1,224,460Inspections Most recent open 2026-07-13 Last loaded 2026-07-16
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Inspection: STRATHMOOR ELECTRIC INC.

Unprogrammed Related inspection · Safety discipline

On , OSHA opened an unprogrammed Related safety inspection of STRATHMOOR ELECTRIC INC. in 333 LORDSHIP BLVD., STRATFORD, CT 06615 (NAICS 238210). OSHA activity number 340902584.

Watch Strathmoor Electric INC. — free Get an email when a new federal OSHA severe-injury report for Strathmoor Electric INC. is published. One employer, no account, unsubscribe in one click.
Site address
333 LORDSHIP BLVD.
City
STRATFORD
State
CT
ZIP
06615
Mailing
1261 STRATFORD AVENUE, STRATFORD, CT 06614
Inspection type
Unprogrammed Related (G)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
5
Ownership type
A

3 citations on file for this inspection.

1926.95 A

Serious Gravity 10 3 instances 4 exposed
Issued
Abate by
Penalty
Initial $2800.00 · Current $1680.00 Reduced
29 CFR 1926.95(a): Personal protective equipment, including personal protective equipment for eyes, face, head, and extremities, protective clothing, respiratory devices, and protective shields and barriers, was not provided, used, or maintained in a sanitary and reliable condition it was necessary by reason of hazards of processes or environment, chemical hazards, radiological hazards, or mechanical irritants encountered in a manner capable of causing injury or impairment in the function of any part of the body through absorption, inhalation, or physical contact.    Electrical Closet:  The employees who were working on and around energized electrical equipment were not provided with the appropriate personal protective equipment (PPE) to protect from electrical hazards, such as (but not limited to) electrical shock, arc flash/arc blast and electrocution.
Recent events (2)
  • — I (S) $1680
  • — Z (S) $2800

1926.416 A01

Serious Gravity 10 3 instances 4 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1926.416(a)(1): Employees were permitted to work in proximity to electric power circuits and were not protected against electric shock by de-energizing and grounding the circuits or effectively guarding the circuits by insulation or other means:  Electrical Closet:  The employer neither de-energized and grounded or effectively guarded nor utilized other effective means prior to permitting employees to work on and around energized electrical distribution panels.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.405 B01

Serious Gravity 5 3 instances 4 exposed
Issued
Abate by
Penalty
Initial $2000.00 · Current $1200.00 Reduced
29 CFR 1926.405(b)(1): Conductors entering boxes, cabinets, and fittings were not protected from abrasion:     Electrical Closet:  The outer sheathing of the cord/conductor that was used to power the fire pump was not protected from sharp edges of the panel box.
Recent events (2)
  • — I (S) $1200
  • — Z (S) $2000

View STRATHMOOR ELECTRIC INC.'s full OSHA safety record →