LEBANON, PA —
OSHA Inspection: CEDAR HAVEN HEALTHCARE CENTER
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of CEDAR HAVEN HEALTHCARE CENTER in 590 SOUTH 5TH AVENUE, LEBANON, PA 17042 (NAICS 621610). OSHA activity number 340905405.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CEDAR HAVEN HEALTHCARE CENTER
- Site address
- 590 SOUTH 5TH AVENUE
- City
- LEBANON
- State
- PA
- ZIP
- 17042
- Mailing
- 590 SOUTH 5TH AVENUE, LEBANON, PA 17042
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 621610
- Employees
- 366
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.219 D01
- Issued
- Oct 26, 2015
- Abate by
- Nov 20, 2015
- Penalty
- Initial $7,000 · Current $5,250 Reduced
General-duty citation text
29 CFR 1910.219(d)(1): Guarding. Pulleys, any parts of which are seven (7) feet or less from the floor or working platform, shall be guarded in accordance with the standards specified in paragraphs (m) and (o) of this section. Pulleys serving as balance wheels (e.g., punch presses) on which the point of contact between belt and pulley is more than six feet six inches (6 ft. 6 in.) from the floor or platform may be guarded with a disk covering the spokes: a) Cedar Haven Healthcare 590 South 5th avenue D-Wing Roof- The belt and pulley that drive the vent motors were not guarded when employees remove the cover to perform maintenance thereby exposing employees to amputation hazards from ingoing nip points, on or about September 8, 2015. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (2)
- — I (S) $5250
- — Z (S) $7000
1910.219 E01 I
- Issued
- Oct 26, 2015
- Abate by
- Nov 20, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.219(e)(1)(i): Where both runs of horizontal belts are seven (7) feet or less from the floor level, the guard shall extend to at least fifteen (15) inches above the belt or to a standard height, except that where both runs of a horizontal belt are 42 inches or less from the floor, the belt shall be fully enclosed in accordance with paragraphs (m) and (o) of this section: a) Cedar Haven Healthcare 590 South 5th avenue D-Wing Roof- The belt and pulley that drive the vent motors were not guarded when employees remove the cover to perform maintenance, thereby exposing employees to amputation hazards from ingoing nip points, on or about September 8, 2015. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.147 C04 I
- Issued
- Oct 26, 2015
- Abate by
- Nov 20, 2015
- Penalty
- Initial $7,000 · Current $5,250 Reduced
General-duty citation text
29 CFR 1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section: a) Cedar Haven Healthcare 590 South 5th avenue D-Wing Roof- Employees perform maintenance and servicing activities on the ventilation motor drive system of 40 ventilation fans. The employer did not develop machine specific lock out/tag out procedures for the ventilation fans, thereby exposing employees to serious injuries including but not limited to; lacerations, amputations, scalping, on or about September 8, 2015. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (2)
- — I (S) $5250
- — Z (S) $7000
More inspections in this industry (NAICS 621610)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340905405.