Planned inspection · Health discipline

On , OSHA opened a planned health inspection of ALLIED FROZEN STORAGE, INC. in 5000 NORTH AMERICA DRIVE, WEST SENECA, NY 14224 (NAICS 493120). OSHA activity number 340909746.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Allied Frozen Storage, INC. — free Get an email when a new federal OSHA severe-injury report for Allied Frozen Storage, INC. is published. One employer, no account, unsubscribe in one click.
Site address
5000 NORTH AMERICA DRIVE
City
WEST SENECA
State
NY
ZIP
14224
Mailing
5000 NORTH AMERICA DRIVE, WEST SENECA, NY 14224
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
493120
Employees
55
Ownership type
A

4 citations on file for this inspection.

1910.119 D03 I B

Serious Gravity 5 2 instances 55 exposed
Issued
Mar 8, 2016
Penalty
Initial $4,500 · Current $3,500 Reduced
29 CFR 1910.119(d)(3)(i)(B): Information pertaining to the equipment in the process did not include piping and instrument diagrams (P&IDs):    (a) Compressor room, vent line, dock, and 3 penthouses - On or about 11/19/15, the fixed ammonia detection system includes sensors AS1, AS2, AS3, AS4, AS5, AS6, AS7, AS8, AS9,  and AS10.  The sensors were not listed on the piping and instrument diagrams.    b) Compressor room - On or about 11/18/15, the LT Accumulator Oil purge valve OP1L was incorrectly marked on the piping and instrument diagram as OP2P.    NO ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $3500
  • — Z (S) $4500

1910.119 D03 II

Serious Gravity 1 1 instance 55 exposed
Issued
Mar 8, 2016
Penalty
Initial $2,700 · Current $0 Reduced
29 CFR 1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices.    (a) Compressor room - On or about 11/19/15, refrigeration valves RP1SV1, RP2SV1, RP3SV1, P1CV1 were not tagged to comply with generally accepted good engineering practices such as, but not limited to, American National Standards Institute/International Institute of Ammonia Refrigeration ANSI/IIAR 2- 1999.       NO ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $0
  • — Z (S) $2700

1910.119 J02

Serious Gravity 5 1 instance 55 exposed
Issued
Mar 8, 2016
Abate by
May 31, 2016
Penalty
Initial $4,500 · Current $3,000 Reduced
29 CFR 1910.119(j)(2): The employer did not implement written procedures to maintain the on-going integrity of process equipment.    a) Plant - On or about 11/17/15  -  The employer's written Mechanical Integrity Program (revised on 7/2/15) states that ASME pressure vessels will receive ultrasonic thickness inspections/tests every 5 years.  The employer has not implemented the Mechanical Integrity Program to maintain the on-going integrity of process equipment.    ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $3000
  • — Z (S) $4500

1910.151 C

Serious Gravity 5 1 instance 55 exposed
Issued
Mar 8, 2016
Abate by
Mar 18, 2016
Penalty
Initial $4,500 · Current $3,000 Reduced
29 CFR 1910.151(c): Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use:    (a) Compressor room - On or about 9/14/15, compressors RC1, RC2, RC3, and RC4 contain 28.34 pounds of anhydrous ammonia, which causes severe skin burns and eye damage.  An eye wash and shower had not been installed.      ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $3000
  • — Z (S) $4500