Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: BUREAU OF PRISONS, FCI FORT WORTH

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of BUREAU OF PRISONS, FCI FORT WORTH in 3150 HORTON ROAD, FORT WORTH, TX 76119 (NAICS 922140). OSHA activity number 340918416.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Bureau of Prisons, FCI Fort Worth — free Get an email when a new federal OSHA severe-injury report for Bureau of Prisons, FCI Fort Worth is published. One employer, no account, unsubscribe in one click.
Site address
3150 HORTON ROAD
City
FORT WORTH
State
TX
ZIP
76119
Mailing
3150 HORTON ROAD, FORT WORTH, TX 76119
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
922140
Employees
356
Ownership type
D

4 citations on file for this inspection.

1910.303 C03 I

Serious Gravity 5 1 instance 1 exposed
Issued
Oct 27, 2015
Abate by
Nov 25, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(c)(3)(i): Conductors were not spliced or joined with splicing devices identified for the use or by brazing, welding, or soldering with a fusible metal or alloy.  Soldered splices were not spliced or joined mechanically and electrically secured first without solder and then soldered.  All splices and joints and the free ends of conductors were not covered with an insulation equivalent to that of the conductors or with an insulating device identified for the purpose.    In the HVAC department, the employer did not ensure that a 120 volt flexible cord used to supply electrical power to the Port A Cool Evaporative Cooler was spliced by brazing, welding, or soldering and protected with its equivalent insulation material were splices had been made exposing employees to electrical shock hazards.   In the Carpenter department, the employer did not ensure that a 120 volt flexible cord used to supply electrical power to the unmarked shop floor fan was spliced by brazing, welding, or soldering and protected with its equivalent insulation material were splices had been made exposing employees to electrical shock hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 G02 I

Serious Gravity 5 1 instance 1 exposed
Issued
Oct 27, 2015
Abate by
Nov 25, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by approved cabinets or other forms of approved enclosures, or other means listed under this provision:  In the HVAC department, the employer did not ensure that the electrical training board electrical conductors were effectively covered exposing employees to electrical shock hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.304 G05

Serious Gravity 5 2 instances 2 exposed
Issued
Oct 27, 2015
Abate by
Nov 25, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:  In the maintenance facilities shops, the employer did not ensure that the shop floor fans cords were equipped with a ground pin exposing employees to electrical shock hazards.  1. Carpenter Shop - Un Marked Shop floor fan. 2. Welding Shop - Airking High Velocity Air Circulator Fan 30
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G01 IV D

Serious Gravity 1 1 instance 1 exposed
Issued
Oct 27, 2015
Abate by
Nov 25, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords and cables were used where attached to building surfaces:  In the HVAC Department, electrical extension cord used to supply electrical power to a Port A Cool Evaporative cooler was attached to the building columns, conduits, and pipe exposing employees to the hazards of electrical shock.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View Bureau of Prisons, FCI Fort Worth's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340918416.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.