BATAVIA, NY —
OSHA Inspection: MULLER QUAKER DAIRY LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of MULLER QUAKER DAIRY LLC in 5140 AGPARK DRIVE, BATAVIA, NY 14020 (NAICS 311520). OSHA activity number 340925262.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- MULLER QUAKER DAIRY LLC
- Site address
- 5140 AGPARK DRIVE
- City
- BATAVIA
- State
- NY
- ZIP
- 14020
- Mailing
- 5140 AGPARK DRIVE, BATAVIA, NY 14020
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 311520
- Employees
- 146
- Ownership type
- A
Citations
8 citations on file for this inspection.
1910.119 E05
- Issued
- Mar 3, 2016
- Abate by
- Apr 3, 2016
- Penalty
- Initial $3,825 · Current $2,869 Reduced
General-duty citation text
29 CFR 1910.119(e)(5): The employer did not assure that PHA recommendations were resolved in a timely manner; a) On or about 09/21/15 in the ammonia system and Engine room; employer failed to protect employees from contact with ammonia vapors and or liquid when they did not add an annual PM of the 3-way relief valves as per recommendation #9 from the PHA conducted 2012. b) On or about 09/21/15 in the ammonia system and Engine room; employer failed to protect employees from contact with ammonia vapors and or liquid when they did not ensure the manufacturer's recommendation for fan blade inspection had been added to the Semi-Annual Condenser PM as per Recommendation #32 from the PHA conducted in 2012. c) On or about 09/21/15 in the ammonia system and Engine Room; employer failed to protect employees from contact with ammonia vapors and or liquid when they did not include in their PM schedule a valve exercising program to comply with IIAR 110.6.6.1 as per recommendation # 53 from the PHA conducted in 2012. ABATEMENT DOCUMENTATION REQUIRED
Recent events (2)
- — I (S) $2868.75
- — Z (S) $3825
1910.119 F01
- Issued
- Mar 3, 2016
- Abate by
- Apr 15, 2016
- Penalty
- Initial $3,060 · Current $2,295 Reduced
General-duty citation text
29 CFR 1910.119(f)(1): The employer did not implement written operating procedures that provide clear instructions for safely conducting activities involved in each covered process. a) On or about 09/21/15 in the Engine Room; employer failed to require the use of a hose connected to the drain line on the oil pots as per Operating Procedures SOP-01, SOP-02, exposing employee(s) involved in oil draining, to ammonia liquid and vapors. ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
- — I (S) $2295
- — Z (S) $3060
1910.119 F04
- Issued
- Mar 3, 2016
- Abate by
- Apr 3, 2016
- Penalty
- Initial $3,825 · Current $2,869 Reduced
General-duty citation text
29 CFR 1910.119(f)(4): The employer did not implement safe work practices to provide for the control of hazards during operations such as control over entrance into a facility by support personnel: a) On or about 09/21/15 in the Machine Room; employer failed to protect the safety of employees when an authorized employee allowed a non authorized employee to enter the equipment room (an authorized area) without an escort, exposing them to contact with ammonia vapors or liquid. ABATEMENT DOCUMENTATION REQUIRED
Recent events (2)
- — I (S) $2868.75
- — Z (S) $3825
1910.119 J02
- Issued
- Mar 3, 2016
- Abate by
- Apr 3, 2016
- Penalty
- Initial $3,825 · Current $2,869 Reduced
General-duty citation text
29 CFR 1910.119(j)(2): The employer did not establish written procedures to maintain the on-going integrity of process equipment; a) On or about 09/21/15 in the Machine room; employer failed to protect employees from exposure to ammonia vapors when they did not have written procedures for performing the preventative maintenance and semi-annual testing of the ammonia detectors, such as but not limited to NH3 AD-1, NH3 AD-2, NH3 AD-3. b) On or about 09/21/15 in the Machine room; employer failed to protect employees from exposure to ammonia vapors when they did not have written procedures for conducting the preventative maintenance and testing of the high level alarms for equipment such as but not limited to, SD-1, HTR. c) On or about 09/21/15 in the Machine room; employer failed to protect employees from exposure to ammonia vapors when they did not have written procedures for conducting the preventative maintenance and testing of the emergency shut down systems on the ammonia compressors. ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
- — I (S) $2868.75
- — Z (S) $3825
1910.119 J04 III
- Issued
- Mar 3, 2016
- Abate by
- Apr 3, 2016
- Penalty
- Initial $3,825 · Current $2,869 Reduced
General-duty citation text
29 CFR 1910.119(j)(4)(iii): The frequency of inspections and tests of process equipment was not consistent with applicable manufacturers' recommendations and good engineering practices, and more frequently if determined to be necessary by prior operating experience. a) On or about 09/21/15 in the Machine room; employer failed to protect employees at the site from ammonia vapors when they did not conduct monthly tests of each AirScan IR ammonia detector sensor(s), record signal voltages, periodically expose sensors to refrigerant sample and log results as per the manufacturers' recommendations for the Honeywell-Manning brand AirScan IR ammonia detector located in the compressor room. ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
- — I (S) $2868.75
- — Z (S) $3825
1910.119 L01
- Issued
- Mar 3, 2016
- Abate by
- Apr 3, 2016
- Penalty
- Initial $3,825 · Current $2,869 Reduced
General-duty citation text
29 CFR 1910.119(l)(1): The employer did not implement procedures to manage changes to process chemicals, technology, equipment, and procedures, and changes to facilities that affect a covered process; a) On or about 09/21/15 in the Engine room; employer failed to require the use of the Management of Change Procedure to authorize a change in the function and operation of the Surge Drum. Due to a malfunction of the level transmitter in the Surge drum, automatic control of the tank levels was turned off. The liquid ammonia level in the tank was controlled manually for a period of 12 hours and to accommodate this change, the pre-set position of the hand expansion valves were changed in order to stabilize the refrigeration system. ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
- — I (S) $2868.75
- — Z (S) $3825
1910.119 L04
- Issued
- Mar 3, 2016
- Abate by
- Apr 3, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.119(l)(4): Process safety information required by paragraph (d) of this section was not updated when a change covered by this paragraph resulted in a change in the process safety information. a) On or about 09/21/15 in the Engine Room; employer failed to change the normal operating range of the Surge drum level (25-40%) in the Process Safety information after establishing a new normal operating range ( 5-25%) due to the replacement of a malfunctioning level transmitter. ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.119 L05
- Issued
- Mar 3, 2016
- Abate by
- Apr 3, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.119(l)(5): When a change covered by this paragraph resulted in a change in the operating procedures or practices required by paragraph (f) of this section, such procedures or practices were not updated accordingly. a) On or about 09/27/15 in the Engine room; employer failed to update the Surge drum operating procedures after switching from automatic control of the tank level to manual operation. Due to a malfunction of the level transmitter in the Surge drum, automatic control of the tank levels was turned off. The liquid ammonia level in the tank was controlled manually for a period of 12 hours and to accommodate this change, the pre-set position on the hand expansion valves were reduced in order to control and stabilize the refrigeration system. ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
- — I (S) $0
- — Z (S) $0