KERMIT, TX —
OSHA Inspection: ENERGY FUTURE HOLDINGS CORP.
Federal Agency inspection · Safety discipline
At a glance
On , OSHA opened a federal Agency safety inspection of ENERGY FUTURE HOLDINGS CORP. in 7 MILES EAST OF KERMIT TX ON E. HWY 115, KERMIT, TX 79745 (NAICS 221122). OSHA activity number 340929371.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ENERGY FUTURE HOLDINGS CORP.
- Site address
- 7 MILES EAST OF KERMIT TX ON E. HWY 115
- City
- KERMIT
- State
- TX
- ZIP
- 79745
- Mailing
- 1616 WOODALL RODGERS FWY, DALLAS, TX 75202
What kind of inspection was it?
- Inspection type
- Federal Agency (M)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 221122
- Employees
- 4500
- Ownership type
- A
Citations
8 citations on file for this inspection.
1910.269 B
- Issued
- Mar 9, 2016
- Abate by
- Apr 4, 2016
- Penalty
- Initial $7,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.269(b): The employer did not provide medical services and first aid as required in 1910.151 On or about September 10, 2015, Oncor Electric Delivery Company LLC did not ensure employees exposed to electric shock were provided medical services and first aid.
Recent events (3)
- — F (S) $0
- — C (S) $7000
- — Z (S) $7000
1910.151 A
- Issued
- Mar 9, 2016
- Abate by
- Apr 4, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.151(a): Medical personnel were not readily available for advice and consultation on matters of plant health: On or about September 10, 2015, Oncor Electric Delivery Company LLC did not ensure medical personnel were readily available for advice and consultation.
Recent events (3)
- — F (S) $0
- — C (S) $0
- — Z (S) $0
1910.269 L02 I C
- Issued
- Mar 9, 2016
- Abate by
- Apr 4, 2016
- Penalty
- Initial $7,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.269(l)(2)(i)(C): Except as provided in paragraph (l)(2)(ii) of this section, at least two employees were not present while an employee performed the following types of work: Installation, removal, or repair of equipment, such as transformers, capacitors, and regulators, if the employee is exposed to contact with parts energized at more than 600 volts, On or about September 10, 2015, Oncor Electric Delivery Company LLC did not ensure at least two qualified employees working on or with exposed energized lines operating at 600 volts or more were present while repairs were made and exposed employees to electric shock hazards.
Recent events (3)
- — F (S) $0
- — C (S) $7000
- — Z (S) $7000
1910.269 L05 I
- Issued
- Mar 9, 2016
- Abate by
- Apr 4, 2016
- Penalty
- Initial $7,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.269(l)(5)(i): The employer did not ensure that each employee, to the extent that other safety-related conditions at the worksite permit, works in a position from which a slip or shock will not bring the employee's body into contact with exposed, un-insulated parts energized at a potential different from the employee's: On or about September 10, 2015 Oncor Electric Delivery Company LLC did not ensure employees worked in a position that would prevent a slip or shock and place the employee's body in contact with exposed un-insulated energized parts.
Recent events (3)
- — F (S) $0
- — C (S) $7000
- — Z (S) $7000
1910.269 L09
- Issued
- Mar 9, 2016
- Abate by
- Apr 4, 2016
- Penalty
- Initial $7,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.269(l)(9): Fuse handling. When an employee must install or remove fuses with one or both terminals energized at more than 300 volts, or with exposed parts energized at more than 50 volts, the employer does not ensure that the employee uses tools or gloves rated for the voltage. When an employee installs or removes expulsion-type fuses with one or both terminals energized at more than 300 volts, the employer does not ensure that the employee wears eye protection meeting the requirements of Subpart I of this part, uses a tool rated for the voltage, and is clear of the exhaust path of the fuse barrel: On or about September 10, 2015 Oncor Electric Delivery Company LLC did not ensure employees installing fuses having one or both terminals energized at more than 300 volts, or with exposed parts energized at more than 50 volts, did not ensure the employees used tools or gloves rated for the voltage. When installing or removing expulsion type fuses with one or both terminals energized at more than 300 volts, does not ensure employees wear eye protection.
Recent events (3)
- — F (S) $0
- — C (S) $7000
- — Z (S) $7000
1910.269 L11
- Issued
- Mar 9, 2016
- Abate by
- Apr 4, 2016
- Penalty
- Initial $7,000 · Current $5,000 Reduced
General-duty citation text
29 CFR 1910.269(l)(11): The employer did not inspect non-current carrying metal parts of equipment or devices, such as transformer cases and circuit-breaker housings, and treat them as energized at the highest voltage to which these parts are exposed, to determine if these parts were grounded before employees begin performing the work: On or about September 10, 2015 Oncor Electric Delivery Company LLC did not inspect noncurrent-carrying metal parts, such as but not limited to meter bases, to determine if the parts were grounded prior to work being performed and exposed employees to electric shock hazards.
Recent events (3)
- — F (O) $5000
- — C (S) $7000
- — Z (S) $7000
1910.269 Q03 VI
- Issued
- Mar 9, 2016
- Abate by
- Apr 4, 2016
- Penalty
- Initial $7,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.269(q)(3)(vi): The employer did not ensure that employees do not perform work when adverse weather conditions would make the work hazardous even after the employer implements the work practices required by this section. Additionally, employees may not perform work when winds reduce the phase-to-phase or phase-to-ground clearances at the work location below the minimum approach distances specified in paragraph (q)(3)(xiv) of this section, unless insulating guards cover the grounded objects and other lines and equipment. Note to paragraph (q)(3)(vi): Thunderstorms in the vicinity, high winds, snow storms, and ice storms are examples of adverse weather conditions that make liveline barehand work too hazardous to perform safely even after the employer implements the work practices required by this section: On or about September 10, 2015 Oncor Electric Delivery Company LLC did not ensure employees working in adverse weather conditions with limited illumination were protected and exposed them to electric shock hazards.
Recent events (3)
- — F (S) $0
- — C (S) $7000
- — Z (S) $7000
1910.333 B02 II C
- Issued
- Mar 9, 2016
- Abate by
- Apr 4, 2016
- Penalty
- Initial $7,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.333(b)(2)(ii)(C): Stored electric energy which might endanger personnel was not released. Capacitors were not discharged and high capacitance elements were not short-circuited and grounded: On or about September 10, 2015, Oncor Electric Delivery Company LLC did not ensure stored electric energy in capacitors was discharged and grounded and exposed employees to electric shock hazards.
Recent events (3)
- — F (S) $0
- — C (S) $7000
- — Z (S) $7000
More inspections at Energy Future Holdings Corp.
View Energy Future Holdings Corp.'s full OSHA safety record →
More inspections in this industry (NAICS 221122)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340929371.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.