OSSEO, WI —
OSHA Inspection: ENERGYS USA, INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of ENERGYS USA, INC. in N47748 US HWY 53, OSSEO, WI 54758 (NAICS 238220). OSHA activity number 340940386.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ENERGYS USA, INC.
- Site address
- N47748 US HWY 53
- City
- OSSEO
- State
- WI
- ZIP
- 54758
- Mailing
- 1987 SPINDT DRIVE P.O. BOX 325, WAUPACA, WI 54981
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238220
- Employees
- 12
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.110 B08 IX
- Issued
- Jan 19, 2016
- Abate by
- Feb 26, 2016
- Penalty
- Initial $2,800 · Current $2,240 Reduced
General-duty citation text
29 CFR 1910.110(b)(8)(ix): After assembly, piping and tubing of all domestic and commercial systems were not tested and proved free of leaks using a manometer or equivalent device that will indicate a drop in pressure (testing shall not be made with a flame): (a) Site located at N47748 US Hwy 53 in Osseo, WI; The gas piping and regulator assemblies were not completed before the vaporizer was started to pressure test system pipes. (b) Site located at N47748 US Hwy 53 in Osseo, WI; The direct fired, vaporizer was used to pressurize pipe assemblies for leak testing operations instead of a manometer.
Recent events (2)
- — I (S) $2240
- — Z (S) $2800
1910.334 D
- Issued
- Jan 19, 2016
- Abate by
- Feb 26, 2016
- Penalty
- Initial $2,800 · Current $1,960 Reduced
General-duty citation text
29 CFR 1910.334(d): Where flammable materials were present only occasionally, such as but not limited to flammable gases, vapors, or liquids; combustible dust; and ignitable fibers or flyings, electrical equipment capable of igniting them shall not be used and measures taken to prevent hazardous conditions from developing were not taken: (a) Site located at N47748 US Hwy 53 in Osseo, WI; Portable electric tools such as but not limited to a pipe threading machine were operated within the classified area around the LPG vaporizer.