Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: UNITED STATES STEEL CORPORATION

Unprogrammed Related inspection · Safety discipline

On , OSHA opened an unprogrammed Related safety inspection of UNITED STATES STEEL CORPORATION in MON VALLEY WORKS - EDGAR THOMSON PLANT BRADDOCK AVENUE AND 13TH STREET, BRADDOCK, PA 15104 (NAICS 331111). OSHA activity number 340955020.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch United States Steel Corporation — free Get an email when a new federal OSHA severe-injury report for United States Steel Corporation is published. One employer, no account, unsubscribe in one click.
Site address
MON VALLEY WORKS - EDGAR THOMSON PLANT BRADDOCK AVENUE AND 13TH STREET
City
BRADDOCK
State
PA
ZIP
15104
Mailing
MON VALLEY WORKS - EDGAR THOMSON PLANT 13TH STREET AND BRADDOCK AVENUE, BRADDOCK, PA 15104
Inspection type
Unprogrammed Related (G)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
331111
Employees
652
Ownership type
A

4 citations on file for this inspection.

1910.303 B06

Serious Gravity 5 1 instance 2 exposed
Issued
Mar 15, 2016
Abate by
Mar 22, 2016
Penalty
Initial $5,000 · Current $5,000
29 CFR 1910.303(b)(6):  Conductors and equipment were located in damp or wet locations:                                                                    a) Wall near abandoned restroom, 3rd floor of BOP shop, Braddock Avenue and 13th Street, Braddock, PA 15104:  Observed on or about November 11, 2015, energized electrical panels and switches (480 volt, 3 phase) were located in a wet location.  Water from leaking from pumps on a higher floor was accumulating on and near the electrical panels and switches.  Employees working on the maintenance and winterization crews were exposed to the hazards of fire and electric shock.
Recent events (3)
  • — F (S) $5000
  • — C (S) $5000
  • — Z (S) $5000

1910.305 G01 IV D

Other-than-serious 2 instances 2 exposed
Issued
Mar 15, 2016
Abate by
Mar 22, 2016
Penalty
Initial $3,000 · Current $0 Reduced
29 CFR 1910.305(g)(1)(iv)(D):  Flexible cords and/or cables were attached to building surfaces:                 a) 3rd floor of BOP shop, near the "F" vessel hood, Braddock Avenue and 13th Street, Braddock, PA 15104:  Observed on or about November 11, 2015, a flexible cord (110 volt power) was attached to building surfaces at various locations along its length.  The cord was being used to supply power to electrical equipment on the third floor of the BOP shop.  Employees working on the maintenance and operations crews were exposed to the hazards of fire and electric shock.      b) 3rd floor of BOP shop, near the "R" vessel hood, Braddock Avenue and 13th Street, Braddock, PA 15104:  Observed on or about November 11, 2015, a flexible cord (110 volt power) was attached to building surfaces at various locations along its length.  The cord was being used to supply power to electrical equipment on the third floor of the BOP shop.  Employees working on the maintenance and operations crews were exposed to the hazards of fire and electric shock.
Recent events (3)
  • — F (O) $0
  • — C (S) $3000
  • — Z (S) $3000

1910.304 G06 VI C 8

Other-than-serious 2 instances 2 exposed
Issued
Mar 15, 2016
Abate by
Mar 22, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.304(g)(6)(vi)(C)(8):  Exposed noncurrent-carrying metal parts of cord-and plug-connected equipment, including portable hand lamps, that may become energized were not grounded:              a) 3rd floor of BOP shop, near "R" vessel hood, Braddock Avenue and 13th Street, Braddock, PA 15104:  Observed on or about November 11, 2015, the metal lamp shade on a portable hand lamp being used to keep a pilot control valve warm was not grounded.  Employees working on the maintenance and winterization crews were exposed to the hazard of fire and electric shock hazards.    b) 3rd floor of BOP shop, near "F" vessel hood, Braddock Avenue and 13th Street, Braddock, PA 15104:  Observed on or about November 11, 2015, the metal lamp shade on a portable hand lamp being used to keep a pilot control valve warm was not grounded.  Employees working on the maintenance and winterization crews were exposed to the hazard of fire and electric shock hazards.
Recent events (3)
  • — F (O) $0
  • — C (O) $0
  • — Z (O) $0

1910.305 G01 II

Other-than-serious 1 instance 2 exposed
Issued
Mar 15, 2016
Abate by
Mar 22, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(ii):  Working space about electric equipment rated 600 volts, nominal, or less was used for storage:                                                                  a) Wall near abandoned restroom, 3rd floor of BOP shop, Braddock Avenue and 13th Street, Braddock, PA 15104:  Observed on or about November 11, 2015, working space about electrical equipment was used for storage.  A hopper filled with water leaking from an upper floor was located directly in front of energized (480 volt, 3 phase) electrical panels and switches.
Recent events (3)
  • — F (O) $0
  • — C (O) $0
  • — Z (O) $0

View United States Steel Corporation's full OSHA safety record →