JACKSON, MS —
OSHA Inspection: COVINGTON ELECTRIC LLC
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of COVINGTON ELECTRIC LLC in 840 BOILING STREET, JACKSON, MS 39202 (NAICS 238210). OSHA activity number 340959212.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- COVINGTON ELECTRIC LLC
- Site address
- 840 BOILING STREET
- City
- JACKSON
- State
- MS
- ZIP
- 39202
- Mailing
- 373 TOLLESON DRIVE, BRANDON, MS 39042
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 11
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.132 D01
- Issued
- Feb 1, 2016
- Abate by
- Feb 3, 2016
- Penalty
- Initial $4,900 · Current $3,900 Reduced
General-duty citation text
29 CFR 1910.132(d)(1): The employer did not assess the workplace to determine if hazards are present, or are likely to be present, which necessitate the use of personal protective equipment: (a) Job Site - On or about October 1, 2015 the employer did not provide low voltage gloves rated for 1000 volts or less to employees doing electrical work on energized wiring rated at 277 volts.
Recent events (2)
- — I (O) $3900
- — Z (S) $4900
1910.137 C02 XII
- Issued
- Feb 1, 2016
- Abate by
- Feb 3, 2016
- Penalty
- Initial $3,500 · Current $2,750 Reduced
General-duty citation text
29 CFR 1910.137(c)(2)(xii): The employer did not certify that electrical protective equipment has been tested in accordance with the requirements of paragraphs (c)(2)(iv), (c)(2)(vii)(D), (c)(2)(viii), (c)(2)(ix), and (c)(2)(xi) of this section. The certification shall identify the equipment that passed the test and the date it was tested and shall be made available upon request to the Assistant Secretary for Occupational Safety and Health and to employees or their authorized representatives. (a) Job Site - On or about October 2, 2015 the employer did not certify that the low voltage gloves given to employees to protect themselves from the hazards of electrical shock were periodically tested.
Recent events (2)
- — I (O) $2750
- — Z (S) $3500
1926.416 A01
- Issued
- Feb 1, 2016
- Abate by
- Feb 9, 2016
- Penalty
- Initial $4,900 · Current $2,500 Reduced
General-duty citation text
29 CFR 1926.416(a)(1): Employee(s) were permitted to work in proximity to electric power circuits that were not protected against electric shock by de-energizing and grounding the circuits or effectively guarding the circuits by insulation or other means: (a) Job Site - On or about October 1, 2015 employees were allowed to break joints, dismantling electric parts, lights, and receptacles without de-energizing the electrical circuit or utilizing personal protective equipment, such as but not limited to, Class 0 rubber gloves rated for maximum use of 1000 volts.
Recent events (2)
- — I (S) $2500
- — Z (S) $4900
1926.416 A03
- Issued
- Feb 1, 2016
- Abate by
- Feb 9, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.416(a)(3): Before work is begun the employer did not ascertain by inquiry or direct observation, or by instruments, whether any part of an energized electric power circuit, exposed or concealed, is so located that the performance of the work may bring any person, tool, or machine into physical or electrical contact with the electric power circuit. The employer did not post and maintain proper warning signs where such a circuit exists. The employer did not advise employees of the location of such lines, the hazards involved, and the protective measures to be taken. (a) Job Site - On or about October 1, 2015 the employer did not locate or identified electrical hazards to employees that were breaking joints and involved in demolition activities while working around energized electrical power circuits.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at Covington Electric LLC
View Covington Electric LLC's full OSHA safety record →
More inspections in this industry (NAICS 238210)
More inspections in MS
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340959212.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.