Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: U.S. POSTAL SERVICE

Complaint inspection · Health discipline

On , OSHA opened a complaint health inspection of U.S. POSTAL SERVICE in 116 OAK STREET, MOORHEAD, IA 51558 (NAICS 491110). OSHA activity number 340964790.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch U.S. Postal Service — free Get an email when a new federal OSHA severe-injury report for U.S. Postal Service is published. One employer, no account, unsubscribe in one click.
Establishment
U.S. POSTAL SERVICE
Site address
116 OAK STREET
City
MOORHEAD
State
IA
ZIP
51558
Mailing
116 OAK STREET, MOORHEAD, IA 51558
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
491110
Employees
1
Ownership type
A

5 citations on file for this inspection.

1910.22 A02

Serious Gravity 5 1 instance 1 exposed
Issued
Mar 24, 2016
Abate by
Apr 14, 2016
Penalty
Initial $7,000 · Current $3,500 Reduced
29 CFR 1910.22(a)(2): Floor(s) of workroom(s) were not maintained in a clean and, so far as possible, a dry condition:    (a) At the US Postal Service in Moorhead, Iowa, on or about September 29, 2015 and prior thereto, the employer did not ensure that the workplace was maintained in a clean condition and dry condition. The office vestibule at the rear of the building had water intrusion.  This condition exposed workers to slip hazard.
Recent events (2)
  • — I (S) $3500
  • — Z (S) $7000

1910.304 B03 I

Deleted Serious Gravity 5 1 instance 1 exposed
Issued
Mar 24, 2016
Abate by
Apr 14, 2016
Penalty
Initial $5,500 · Current $0 Reduced
29 CFR 1910.304(b)(3)(i): All 125-volt, single-phase, 15- and 20-ampere receptacles installed in bathrooms or on rooftops were not equipped with ground-fault circuit-interrupter protection for personnel.  (a)  In the bathroom at the Moorhead Post Office, a standard 125 volt single 15 or 20 ampere receptacle was not suitably equipped with ground-fault circuit-interrupter protection.  The receptacle supplied power for an electric tankless water heater on the wall above the toilet.  This condition exposed employees to fire and electrical hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $5500

1910.305 E01

Serious Gravity 10 1 instance 1 exposed
Issued
Mar 24, 2016
Abate by
Apr 14, 2016
Penalty
Initial $7,000 · Current $3,500 Reduced
29 CFR 1910.305(e)(1): Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in damp or wet locations were not installed to prevent moisture or water from entering and accumulating within the enclosures    (a) In the vestibule leading to the back door, a circuit breaker box used as a junction box was not installed to prevent moisture and/or water from entering the box.  The box was exposed to water intrusion from the ceiling and when water that traveled down the wall to the box.  This condition exposed workers to fire and electrical hazards.
Recent events (2)
  • — I (S) $3500
  • — Z (S) $7000

1910.305 J02 IV

Serious Gravity 10 1 instance 1 exposed
Issued
Mar 24, 2016
Abate by
Apr 14, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(j)(2)(iv): A receptacle installed in a wet or damp location was not suitable for the location:  (a) On the exterior of the building leading into the back door, a receptacle was not designed to prevent moisture and/or water from entering the receptacle.  The unit was located on the exterior wall where water intrusion from the rain and condensate could get into the unit.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.334 A03 III

Repeat Gravity 5 1 instance 1 exposed
Issued
Mar 24, 2016
Abate by
Apr 14, 2016
Penalty
Initial $44,000 · Current $22,000 Reduced
29 CFR 1910.334(a)(3)(iii): Adapters which interrupt the continuity of the equipment grounding connection were used:    (a)  At the temporary desk for the Blencoe office, the continuity to ground was interrupted between a 2-prong 125 volt wall receptacle used to provide power to a 3-prong relocatable power tap (RPT) when an AC three-prong to two-prong plug adapter was used.  This condition exposed workers to a fire and electrical hazard.    The US Postal Service was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.334(a)(3)(iii), which was contained in OSHA inspection number 1004473, citation number 1, item number 3 and was affirmed as a final order on 02/17/2015, with respect to a workplace located at 100 East 3rd Ave, Ellensburg, WA 98926.
Recent events (2)
  • — I (R) $22000
  • — Z (R) $44000

View U.S. Postal Service's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340964790.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.