Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: AXIS CONSTRUCTION, LLC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of AXIS CONSTRUCTION, LLC in 1-11 EAST GAY STREET, COLUMBUS, OH 43215 (NAICS 236118). OSHA activity number 340973908.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Axis Construction, LLC — free Get an email when a new federal OSHA severe-injury report for Axis Construction, LLC is published. One employer, no account, unsubscribe in one click.
Site address
1-11 EAST GAY STREET
City
COLUMBUS
State
OH
ZIP
43215
Mailing
4427 PROFESSIONAL PARKWAY, GROVEPORT, OH 43125
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
236118
Employees
14
Ownership type
A

3 citations on file for this inspection.

1926.403 E

Serious Gravity 5 1 instance 5 exposed
Issued
Dec 8, 2015
Penalty
Initial $2,000 · Current $1,200 Reduced
29 CFR 1926.403(e): Splices. Conductors shall be spliced or joined with splicing devices designed for the use or by brazing, welding, or soldering with a fusible metal or alloy. Soldered splices shall first be so spliced or joined as to be mechanically and electrically secure without solder and then soldered. All splices and joints and the free ends of conductors shall be covered with an insulation equivalent to that of the conductors or with an insulating device designed for the purpose.  a. In the stair well leading to the basement, the free end of the conductor was not covered with an insulation equivalent or device designed for the purpose, thereby exposing employees to an electrical hazard.
Recent events (2)
  • — I (S) $1200
  • — Z (S) $2000

1926.405 B01

Serious Gravity 5 1 instance 4 exposed
Issued
Dec 8, 2015
Penalty
Initial $2,000 · Current $1,200 Reduced
29 CFR 1926.405(b)(1): Conductors entering boxes, cabinets, or fittings. Conductors entering boxes, cabinets, or fittings shall be protected from abrasion, and openings through which conductors enter shall be effectively closed. Unused openings in cabinets, boxes, and fittings shall also be effectively closed.  a. On the 4th floor, the panel box had 4 unused openings, thereby exposing employees to an electrical hazard.
Recent events (2)
  • — I (S) $1200
  • — Z (S) $2000

1926.405 G02 V

Serious Gravity 5 2 instances 4 exposed
Issued
Dec 8, 2015
Penalty
Initial $2,000 · Current $1,200 Reduced
29 CFR 1926.405(g)(2)(v): Cords passing through holes. Flexible cords and cables shall be protected by bushings or fittings where passing through holes in covers, outlet boxes, or similar enclosures.  a. On the 4th floor, the service main was not protected from abrasion while entering the box, thereby exposing employees to an electrical hazard.  b. In the basement, the main service disconnect switch box had two cables entering the box without a bushing or other protective sleeve to prevent abrasion, thereby exposing employees to an electrical hazard.
Recent events (2)
  • — I (S) $1200
  • — Z (S) $2000

View Axis Construction, LLC's full OSHA safety record →