Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: FRANKLIN PONCE

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of FRANKLIN PONCE in 560 PALLDALE DRIVE, SCOTTDALE, GA 30079 (NAICS 238210). OSHA activity number 340980580.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Franklin Ponce — free Get an email when a new federal OSHA severe-injury report for Franklin Ponce is published. One employer, no account, unsubscribe in one click.
Establishment
FRANKLIN PONCE
Site address
560 PALLDALE DRIVE
City
SCOTTDALE
State
GA
ZIP
30079
Mailing
1507 HICKORY VALLEY, CHATTANOOGA, TN 37421
Inspection type
Unprogrammed Other (I)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
6
Ownership type
A

3 citations on file for this inspection.

1926.403 I02 I A

Serious Gravity 10 1 instance 1 exposed
Issued
Mar 2, 2016
Abate by
Mar 28, 2016
Penalty
Initial $2,800 · Current $1,680 Reduced
29 CFR 1926.403(i)(2)(i)(A): Live parts of electric equipment operating at 50 volts or more were not kept in a room, vault, or similar enclosure accessible only to qualified persons:  On or about October 8, 2015 on the fourth floor of building 210 other than qualified persons had access to the access to the electrical room.  Inside the electrical room on the fourth floor, the 120/240 electrical panel was energized to provide power to the temporary lights and outlets.
Recent events (2)
  • — I (S) $1680
  • — Z (S) $2800

1926.405 D

Serious Gravity 10 1 instance 2 exposed
Issued
Mar 2, 2016
Abate by
Mar 28, 2016
Penalty
Initial $0 · Current $0
29 CFR 1926.405(d): Panelboards mounted in cabinets, cutout boxes or enclosures designed for the purpose were not dead front:   On or about October 8, 2015 on the fourth floor of building 210, inside the electrical room on the fourth floor, the 120/240 electrical panel was energized to provide power to the temporary lights and outlets and the dead front was not installed.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.405 A02 II C

Serious Gravity 5 1 instance 1 exposed
Issued
Mar 2, 2016
Abate by
Mar 28, 2016
Penalty
Initial $1,600 · Current $960 Reduced
29 CFR 1926.405(a)(2)(ii)(C): Receptacles used on temporary wiring were not of the grounding type:   On or about October 8, 2015 on the second floor of building 210 employees using tools and other equipment were exposed to electric shock as the outlet they received power from had an open ground.
Recent events (2)
  • — I (S) $960
  • — Z (S) $1600

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340980580.