SCOTTDALE, GA —
OSHA Inspection: FRANKLIN PONCE
Unprogrammed Other inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Other safety inspection of FRANKLIN PONCE in 560 PALLDALE DRIVE, SCOTTDALE, GA 30079 (NAICS 238210). OSHA activity number 340980580.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- FRANKLIN PONCE
- Site address
- 560 PALLDALE DRIVE
- City
- SCOTTDALE
- State
- GA
- ZIP
- 30079
- Mailing
- 1507 HICKORY VALLEY, CHATTANOOGA, TN 37421
What kind of inspection was it?
- Inspection type
- Unprogrammed Other (I)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 6
- Ownership type
- A
Citations
3 citations on file for this inspection.
1926.403 I02 I A
- Issued
- Mar 2, 2016
- Abate by
- Mar 28, 2016
- Penalty
- Initial $2,800 · Current $1,680 Reduced
General-duty citation text
29 CFR 1926.403(i)(2)(i)(A): Live parts of electric equipment operating at 50 volts or more were not kept in a room, vault, or similar enclosure accessible only to qualified persons: On or about October 8, 2015 on the fourth floor of building 210 other than qualified persons had access to the access to the electrical room. Inside the electrical room on the fourth floor, the 120/240 electrical panel was energized to provide power to the temporary lights and outlets.
Recent events (2)
- — I (S) $1680
- — Z (S) $2800
1926.405 D
- Issued
- Mar 2, 2016
- Abate by
- Mar 28, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.405(d): Panelboards mounted in cabinets, cutout boxes or enclosures designed for the purpose were not dead front: On or about October 8, 2015 on the fourth floor of building 210, inside the electrical room on the fourth floor, the 120/240 electrical panel was energized to provide power to the temporary lights and outlets and the dead front was not installed.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1926.405 A02 II C
- Issued
- Mar 2, 2016
- Abate by
- Mar 28, 2016
- Penalty
- Initial $1,600 · Current $960 Reduced
General-duty citation text
29 CFR 1926.405(a)(2)(ii)(C): Receptacles used on temporary wiring were not of the grounding type: On or about October 8, 2015 on the second floor of building 210 employees using tools and other equipment were exposed to electric shock as the outlet they received power from had an open ground.
Recent events (2)
- — I (S) $960
- — Z (S) $1600
More inspections in this industry (NAICS 238210)
More inspections in GA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340980580.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.