OSHA Inspection: LEI COMPANIES, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of LEI COMPANIES, INC. in 9191 GRANT ST., THORNTON, CO 80229 (NAICS 238210). OSHA activity number 340997220.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch LEI Companies, INC. — free Get an email when a new federal OSHA severe-injury report for LEI Companies, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
LEI COMPANIES, INC.
Site address
9191 GRANT ST.
City
THORNTON
State
CO
ZIP
80229
Mailing
2017 CURTIS ST., DENVER, CO 80205
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
150
Ownership type
A

3 citations on file for this inspection.

1926.416 A01

Serious Gravity 5 1 instance 2 exposed
Issued
Apr 1, 2016
Abate by
Apr 27, 2016
Penalty
Initial $3,825 · Current $2,869 Reduced
29 CFR 1926.416(a)(1): Employees were permitted to work in proximity to electric power circuits and were not protected against electric shock by de-energizing and grounding the circuits or effectively guarding the circuits by insulation or other means:         (a)  LEI Companies, Inc. at 9191 Grant Street, Thornton, CO 80229: On or before October 9, 2015, the employer did not ensure that employees working on the electric power circuit in the MRI electrical room at North Suburban Medical Center were protected from electric shock by de-energizing the circuit before work begun. The employees were making a tie-in to a neutral conductor that was being shared with at least one other live circuit. This condition resulted in both employees receiving an electric shock of 277 V, phase to ground and one of the employees being hospitalized after the incident.
Recent events (2)
  • — I (S) $2869
  • — Z (S) $3825

1926.416 A03

Serious Gravity 5 1 instance 2 exposed
Issued
Apr 1, 2016
Abate by
Apr 27, 2016
Penalty
Initial $0 · Current $0
29 CFR 1926.416(a)(3): Employer did not advise employees of the location of energized electrical power circuits, the hazards involved, and the protective measures to be taken:      (a)  LEI Companies, Inc. at 9191 Grant Street, Thornton, CO 80229: On or before October 9, 2015, the employer did not ensure employees working on the electric power circuit in the MRI electrical room at North Suburban Medical Center were advised of the location of energized electrical power circuits, the hazards involved, and the protective measures to be taken before work begun. The employees were making a tie-in to a neutral conductor that was being shared with at least one other live circuit. This condition resulted in both employees receiving an electric shock of 277 V, phase to ground and one of the employees being hospitalized after the incident.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.20 B02

Other-than-serious 1 instance 2 exposed
Issued
Apr 1, 2016
Abate by
Apr 27, 2016
Penalty
Initial $3,825 · Current $2,869 Reduced
29 CFR 1926.20(b)(2):  The employer did not initiate and maintain a safety program which provides for frequent and regular inspections of jobsites, materials, and equipment to be made by a competent person (i.e., a person who is capable of identifying existing and predictable hazards in the surroundings or working conditions which are unsanitary, hazardous, or dangerous to employees, and who has the authority to take prompt corrective measures to eliminate them):      (a)  LEI Companies, Inc. at 9191 Grant Street, Thornton, CO 80229: On or before October 9, 2015, the employer did not ensure that a safety program was developed and implemented for the work environment to include regular inspections of the job-site, materials, and equipment; conducted by a competent person. Two employees engaged in electrical work activities were exposed to shock hazards because they did not adequately deenergize and test for energized circuits while in the MRI electrical room at North Suburban Medical Center. The employees were making a tie-in to a neutral conductor that was being shared with at least one other live circuit. This condition resulted in both employees receiving an electric shock of 277 V, phase to ground and one of the employees being hospitalized after the incident.
Recent events (2)
  • — I (O) $2869
  • — Z (S) $3825

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340997220.