Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: THE TAPCO TUBE COMPANY INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of THE TAPCO TUBE COMPANY INC. in 10721 E. WATER STREET EXTENSION, MEADVILLE, PA 16335 (NAICS 331210). OSHA activity number 341002673.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch The Tapco Tube Company INC. — free Get an email when a new federal OSHA severe-injury report for The Tapco Tube Company INC. is published. One employer, no account, unsubscribe in one click.
Site address
10721 E. WATER STREET EXTENSION
City
MEADVILLE
State
PA
ZIP
16335
Mailing
10721 E. WATER STREET EXTENSION, MEADVILLE, PA 16335
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
331210
Employees
52
Ownership type
A

4 citations on file for this inspection.

1910.303 G02 I

Serious Gravity 10 1 instance 2 exposed
Issued
Nov 6, 2015
Abate by
Dec 4, 2015
Penalty
Initial $4,900 · Current $4,900
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):   A.)  The Tapco Tube Company Inc., 2nd floor high voltage room, Electrical Systems Box for the Welder - On or about 10/12/15, and at times prior thereto, a 480 volt electrical panel box was left unattended without the cover being placed back on the panel box.  The room where the box was located what not locked or in anyway restricted from unqualified personnel entering the room while the cover was off of the panel box.
Recent events (2)
  • — I (S) $4900
  • — Z (S) $4900

1910.335 B01

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Nov 6, 2015
Abate by
Dec 4, 2015
Penalty
Initial $4,900 · Current $0 Reduced
29 CFR 1910.335(b)(1): Safety signs, safety symbols, or accident prevention tags were not used where necessary to warn employees about electrical hazards which may endanger them:  A.)  The Tapco Tube Company Inc., 2nd floor high voltage room, Electrical Systems Box for the Welder - - On or about 10/12/15, and at times prior thereto, signage was not used to inform unqualified employees that the cover on the 480 volt box for the welder in the high voltage room was removed.  The electrical hazards were created by a cover being left off of a 480 volt electrical box for the welder in the high voltage room.  While the cover was off, the electrical  parts inside the box were energized.
Recent events (2)
  • — I (S) $0
  • — Z (S) $4900

1910.335 B02

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Nov 6, 2015
Abate by
Dec 4, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.335(b)(2): Barricades were not used in conjunction with safety signs where it was necessary to prevent or limit employee access to work areas in which employees were exposed to uninsulated energized conductors or circuit parts:   A.)  The Tapco Tube Company Inc./2nd floor high voltage room, Electrical Systems Box for the Welder: On or about 10/12/15, and at times prior thereto, barricades and signage were not used to inform employees and deter access to the electrical hazards.  The electrical hazards were created by a cover being left off of a 480 volt electrical box for the welder in the high voltage room.  While the cover was off, the electrical  parts inside the box were energized.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 H02 I

Deleted Serious Gravity 5 1 instance 2 exposed
Issued
Nov 6, 2015
Abate by
Dec 4, 2015
Penalty
Initial $3,500 · Current $0 Reduced
29 CFR 1910.303(h)(2)(i): Electrical installations in a vault, room, or closet or in an area surrounded by a wall, screen, or fence, access to which was not controlled by lock and key or other approved means, was accessible to unqualified persons only.   A.)  The Tapco Tube Company Inc.,; high voltage room; 2nd floor - On or about 10/12/15, and at times prior thereto, electrical equipment was not located in an area that made it accessible only to qualified personnel.  The electrical high voltage room was located on a 2nd floor but the room was not locked or restricted through other equally effective means to prevent unqualified employees from entering it.
Recent events (2)
  • — I (S) $0
  • — Z (S) $3500

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341002673.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.