BAYTOWN, TX —
OSHA Inspection: SPEEDCO
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of SPEEDCO in 2110 EAST FREEWAY, BAYTOWN, TX 77521 (NAICS 811111). OSHA activity number 341025088.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- SPEEDCO
- Site address
- 2110 EAST FREEWAY
- City
- BAYTOWN
- State
- TX
- ZIP
- 77521
- Mailing
- 2110 EAST FREEWAY, BAYTOWN, TX 77521
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 811111
- Employees
- 19
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.333 A01
- Issued
- Nov 23, 2015
- Abate by
- Nov 30, 2015
- Penalty
- Initial $5,000 · Current $3,500 Reduced
General-duty citation text
29 CFR 1910.333(a)(1): Live parts to which an employee was exposed were not deenergized before the employee worked on or near them: On or about October 27, 2015, in the storage area of the facility where an employee was exposed an electrical hazard while changing out 277 volt light bulbs without deenergizing the live part.
Recent events (2)
- — I (S) $3500
- — Z (S) $5000
1910.303 F02
- Issued
- Nov 23, 2015
- Abate by
- Dec 4, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: On or about October 27, 2015, in the compressor room where two breaker boxes containing several feeders and branch circuits were being used to provide power throughout the facility without having all of the disconnecting means or overcurrent devices labeled for its purpose or arranged so that the purpose was evident.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.303 G01
- Issued
- Nov 23, 2015
- Abate by
- Nov 30, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: On or about October 27, 2015, in the compressor room where two breaker boxes used by employees were without sufficient access and working space.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Speedco
View Speedco's full OSHA safety record →
More inspections in this industry (NAICS 811111)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341025088.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.