Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ASSOCIATION FOR INDIVIDUAL DEVELOPMENT ELGIN TRAINING CENTER

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of ASSOCIATION FOR INDIVIDUAL DEVELOPMENT ELGIN TRAINING CENTER in 1135 BOWES ROAD, ELGIN, IL 60123 (NAICS 623110). OSHA activity number 341031912.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Association for Individual Development Elgin Training Center — free Get an email when a new federal OSHA severe-injury report for Association for Individual Development Elgin Training Center is published. One employer, no account, unsubscribe in one click.
Site address
1135 BOWES ROAD
City
ELGIN
State
IL
ZIP
60123
Mailing
1135 BOWES ROAD, ELGIN, IL 60123
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
623110
Employees
50
Ownership type
A

2 citations on file for this inspection.

1910.36 D01

Serious Gravity 1 1 instance 50 exposed
Issued
Nov 6, 2015
Abate by
Dec 2, 2015
Penalty
Initial $2,550 · Current $1,530 Reduced
29 CFR 1910.36(d)(1): Employees must be able to open an exit route door from the inside at all times without keys, tools, or special knowledge. A device such as a panic bar that locks only from the outside is permitted on exit discharge doors.    Employee(s) were not able to open exit route door #2 from the inside at all times without keys, tools, or special knowledge. This exposed employees to a smoke inhalation or burn in case of a fire.    Abatement documentation is required for this item in accordance with 29 CFR 1903.19(d).
Recent events (2)
  • — I (S) $1530
  • — Z (S) $2550

1910.37 B06

Serious Gravity 1 1 instance 50 exposed
Issued
Nov 6, 2015
Abate by
Nov 27, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(6): Each exit sign must be illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color. Self-luminous or electroluminescent signs that have a minimum luminance surface value of at least .06 footlamberts (0.21 cd/m2) are permitted.   The employer did not ensure that each exit sign was illuminated to the required surface value. This exposed employees to smoke inhalation and burns in the case of a fire.  Abatement documentation is required for this item in accordance with 29 CFR 1903.19(d).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341031912.