Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: PRIORITY WIRE & CABLE, INC.

Unprogrammed Related inspection · Safety discipline

On , OSHA opened an unprogrammed Related safety inspection of PRIORITY WIRE & CABLE, INC. in 1800 E. ROOSEVELT RD., LITTLE ROCK, AR 72206 (NAICS 335921). OSHA activity number 341033629.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Priority Wire & Cable, INC. — free Get an email when a new federal OSHA severe-injury report for Priority Wire & Cable, INC. is published. One employer, no account, unsubscribe in one click.
Site address
1800 E. ROOSEVELT RD.
City
LITTLE ROCK
State
AR
ZIP
72206
Mailing
1800 E. ROOSEVELT RD., LITTLE ROCK, AR 72206
Inspection type
Unprogrammed Related (G)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
335921
Employees
85
Ownership type
A

6 citations on file for this inspection.

1910.212 A01

Serious Gravity 10 1 instance 2 exposed
Issued
Dec 1, 2015
Penalty
Initial $7,000 · Current $4,200 Reduced
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:    The Strip-Tec wire stripper with model 3000 was not guarded at the point of operation exposing the operator to rotating parts.
Recent events (2)
  • — I (S) $4200
  • — Z (S) $7000

1910.303 E01 I

Other-than-serious 1 instance 3 exposed
Issued
Dec 1, 2015
Abate by
Dec 9, 2015
Penalty
Initial $3,000 · Current $6,000
29 CFR 1910.303(e)(1)(i): Electric equipment was used without the manufacturer's name, trademark, or other descriptive marking by which the organization responsible for the product could be identified:    The circuit breaker panel located near the Scrap Department lacked any type of marking that would indicate it's manufacturer.
Recent events (2)
  • — I (O) $6000
  • — Z (S) $3000

1910.303 E01 II

Other-than-serious 1 instance 3 exposed
Issued
Dec 1, 2015
Abate by
Dec 9, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(e)(1)(ii): Electric equipment was used without markings giving voltage, current, wattage, or other ratings as necessary:    The circuit breaker panel near the Scrap Department lacked any type of marking indicating the voltage or current.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.303 F02

Other-than-serious 1 instance 3 exposed
Issued
Dec 1, 2015
Abate by
Dec 9, 2015
Penalty
Initial $6,000 · Current $0 Reduced
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:    The circuit breaker panel near the Scrap Department was not marked to indicate each breakers purpose nor was it arranged so the purpose was evident.
Recent events (2)
  • — I (O) $0
  • — Z (S) $6000

1910.334 A02 I

Serious Gravity 5 1 instance 2 exposed
Issued
Dec 1, 2015
Abate by
Dec 9, 2015
Penalty
Initial $5,000 · Current $3,000 Reduced
29 CFR 1910.334(a)(2)(i): Portable cord and plug connected equipment and flexible cord sets (extension cords) were not visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket):    The sheathing for the cord of the Strip-Tec wire stripper with model 3300 had pulled from the manufacture installed control box exposing insulated conductors which were not protected from damage. The employer had not ensured the cord was visually inspected before us on any shift for external defects, exposing employees to electrical hazards.
Recent events (2)
  • — I (S) $3000
  • — Z (S) $5000

1910.145 C02 I

Other-than-serious 2 instances 2 exposed
Issued
Dec 1, 2015
Abate by
Dec 9, 2015
Penalty
Initial $1,000 · Current $600 Reduced
29 CFR 1910.145(c)(2)(i): Caution signs were not used to warn against potential hazards or to caution against unsafe practices:    The Strip-Tec wire stripper with model 3000 did not have the manufacturer's caution tags exposing employees to caught-in hazards on the machine as follows:    a. Caution: Do not operate without guards in place.    b. Caution: Keep hands clear.
Recent events (2)
  • — I (O) $600
  • — Z (O) $1000

View Priority Wire & Cable, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341033629.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.