Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: FEDERAL PROTECTIVE SERVICE, REGION 10 PACIFIC NW / ARCTIC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of FEDERAL PROTECTIVE SERVICE, REGION 10 PACIFIC NW / ARCTIC in 400 15TH STREET SW 2ND FLOOR, AUBURN, WA 98001 (NAICS 922120). OSHA activity number 341034569.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Federal Protective Service, Region 10 Pacific NW / Arctic — free Get an email when a new federal OSHA severe-injury report for Federal Protective Service, Region 10 Pacific NW / Arctic is published. One employer, no account, unsubscribe in one click.
Site address
400 15TH STREET SW 2ND FLOOR
City
AUBURN
State
WA
ZIP
98001
Mailing
400 15TH STREET SW 2ND FLOOR, AUBURN, WA 98001
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
922120
Employees
27
Ownership type
D

2 citations on file for this inspection.

1910.303 B02

Serious Gravity 1 7 instances 14 exposed
Issued
Dec 1, 2015
Abate by
Jan 3, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  (a)  Conference Room;  A power strip was plugged into another power strip (relocatable power tap) which powered a projector and other audiovisual equipment. The UL listing states that relocatable power taps are designed to be plugged into an outlet, and not daisy chained and plugged into other relocatable power taps or extension cords.  This exposes employees to possible electrical fire hazards.    (b)  Special Agents Room, Cubicle by window on left:  A power strip was plugged into an extension cord which was plugged into another extension cord (daisy chain). The power strip powered computer equipment. The UL listing states that relocatable power taps are designed to be plugged into an outlet, and not daisy chained and plugged into other relocatable power taps or extension cords.  This exposes employees to possible electrical fire hazards.    (c)  Special Agents Room,  Middle cubicle on right: A power strip was plugged into another power strip which powered computer equipment. The UL listing states that relocatable power taps are designed to be plugged into an outlet, and not daisy chained and plugged into other relocatable power taps or extension cords.  This exposes employees to possible electrical fire hazards.    (d)  Inspector Cubicle Adjacent to Tacoma Group;  A white power strip was plugged into another white power strip which powered computer equipment. The UL listing states that relocatable power taps are designed to be plugged into an outlet, and not daisy chained and plugged into other relocatable power taps or extension cords.  This exposes employees to possible electrical fire hazards.    (e)          District Command Cubicles:  Three white power strips were plugged into each other which powered computer equipment. The UL listing states that relocatable power taps are designed to be plugged into an outlet, and not daisy chained and plugged into other relocatable power taps or extension cords.  This exposes employees to possible electrical fire hazards.    (f)  Regional Director Work Area;  An Amana microwave, Mr. Coffee coffee pot and a Kitchen Aid grinder were plugged into a power strip which was not rated for appliances. The UL listing states that relocatable power taps are designed for low amperage computer and audiovisual types of equipment, and not appliances.  This exposes employees to possible electrical fire hazards.    (g)  District Command Area;  A Panasonic microwave, Vizio TV and Absocold refrigerator were plugged into a power strip which was not rated for appliances. The UL listing states that relocatable power taps are designed for low amperage computer and audiovisual types of equipment, and not appliances.  This exposes employees to possible electrical fire hazards.
Recent events (1)
  • — Z (S) $0

1910.303 G01 II

Other-than-serious 2 instances 7 exposed
Issued
Dec 1, 2015
Abate by
Jan 3, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:  a)      Warehouse:  There was a metal storage cabinet stored underneath a breaker panel which was labeled fitness center panel.   b)      Warehouse Open Bay;  Chairs and boxes were stored in front of the breaker panels.
Recent events (1)
  • — Z (O) $0

View Federal Protective Service, Region 10 Pacific NW / Arctic's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341034569.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.