FALL RIVER, MA —
OSHA Inspection: LACOMB ENTERPRISES, INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of LACOMB ENTERPRISES, INC. in 133 MARIANO S. BISHOP BOULEVARD, FALL RIVER, MA 02724 (NAICS 453998). OSHA activity number 341036465.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- LACOMB ENTERPRISES, INC.
- Site address
- 133 MARIANO S. BISHOP BOULEVARD
- City
- FALL RIVER
- State
- MA
- ZIP
- 02724
- Mailing
- 133 MARIANO S. BISHOP BOULEVARD, FALL RIVER, MA 02724
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 453998
- Employees
- 22
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.141 D02 II
- Issued
- Nov 13, 2015
- Abate by
- Jan 6, 2016
- Penalty
- Initial $2,100 · Current $2,100
General-duty citation text
29 CFR 1910.141(d)(2)(ii): Lavatories were not provided with hot and cold, or tepid running water: Within the store lavatories were not provided with hot or tepid running water.
Recent events (1)
- — Z (S) $2100
1910.303 F02
- Issued
- Nov 13, 2015
- Abate by
- Jan 6, 2016
- Penalty
- Initial $2,100 · Current $2,100
General-duty citation text
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: (a) Old TV Room: The circuit breakers in the electrical panels were not clearly labeled nor was the purpose evident. (b) Front Storage Closet: The circuit breakers in the electrical panels were not clearly labeled nor was the purpose evident (c) Rear Storage Closet: The circuit breakers in the electrical panels were not clearly labeled nor was the purpose evident. (d) Receiving area: The circuit breakers in the electrical panels were not clearly labeled nor was the purpose evident
Recent events (1)
- — Z (S) $2100
1910.303 G01 II
- Issued
- Nov 13, 2015
- Abate by
- Jan 6, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: (a) Old TV Room: The required space about the electrical panels was used for storage of signs, packing material, and metal pallets. (b) Front Storage Closet: The required space about the electrical panels was used for storage of signs (c) Rear Storage Closet: The required space about the electrical panels was used for the storage of hazardous aerosol material. (d) Receiving area: The required space around the electrical panels was used for the storage of cardboard pieces, boxes of products, and a snow shovel.
Recent events (1)
- — Z (S) $0
1910.304 F01 VIII
- Issued
- Nov 13, 2015
- Abate by
- Jan 6, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(f)(1)(viii): Circuit breakers for circuits rated 600 volts, nominal, or less used as switches in 120 volt and 227 volt fluorescent lighting circuits, were not listed and marked "SWD" Front Storage Closet: Employees used circuit breakers to turn on and off the lights in the store where the circuit breakers were not listed and marked "SWD"
Recent events (1)
- — Z (S) $0
1910.1200 E01
- Issued
- Nov 13, 2015
- Abate by
- Jan 6, 2016
- Penalty
- Initial $2,100 · Current $2,100
General-duty citation text
29 CFR 1910.1200(e)(1): The employer did not develop, implement, and/or maintain at the workplace a written hazard communication program which describes how the criteria specified in 29 CFR 1910.1200(f) labeling, (g) safety data sheets, and (h) training will be met: Facility: A written hazard communication program was not developed and implemented where employees used hazardous chemical products during floor maintenance operations.
Recent events (1)
- — Z (S) $2100
More inspections at Lacomb Enterprises, INC.
View Lacomb Enterprises, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 453998)
More inspections in MA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341036465.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.