Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: POLAR CORPORATION

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of POLAR CORPORATION in 59 HIGH STREET, SUITE 11, NEW BRITAIN, CT 06051 (NAICS 336412). OSHA activity number 341056596.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Polar Corporation — free Get an email when a new federal OSHA severe-injury report for Polar Corporation is published. One employer, no account, unsubscribe in one click.
Establishment
POLAR CORPORATION
Site address
59 HIGH STREET, SUITE 11
City
NEW BRITAIN
State
CT
ZIP
06051
Mailing
P.O. BOX 24, NEW BRITAIN, CT 06051
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
336412
Employees
29
Ownership type
A

12 citations on file for this inspection.

1910.37 A03

Serious Gravity 5 1 instance 29 exposed
Issued
Dec 1, 2015
Abate by
Jan 20, 2016
Penalty
Initial $3,500 · Current $1,750 Reduced
29 CFR 1910.37(a)(3): Exit routes were not kept free and unobstructed.  Materials or equipment were placed, either permanently or temporarily, within the exit route:  A.  On or about November 19, 2015, Production Shop:  The exit route to the side-hinged fire door near the bay door was reduced to 17 inches by the placement of a piece of pallet changing equipment.
Recent events (2)
  • — I (S) $1750
  • — Z (S) $3500

1910.37 B02

Serious Gravity 5 1 instance 29 exposed
Issued
Dec 1, 2015
Abate by
Jan 20, 2016
Penalty
Initial $3,500 · Current $1,750 Reduced
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit":  A.  On or about November 19, 2015, Production Shop:  There was no "EXIT" sign on or near the side-hinged fire door near the bay door.
Recent events (2)
  • — I (S) $1750
  • — Z (S) $3500

1910.37 B04

Serious Gravity 5 1 instance 29 exposed
Issued
Dec 1, 2015
Abate by
Jan 20, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(4): Signs were not posted along the exit access indicating the direction of travel to the nearest exit and exit discharge when the direction of travel to the exit or exit discharge was not immediately apparent:  A.  On or about November 19, 2015, Production Shop:  The emergency exit route was not identified within the shop.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.37 B05

Serious Gravity 5 1 instance 29 exposed
Issued
Dec 1, 2015
Abate by
Jan 20, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(5): Each doorway or passage along an exit access that could be mistaken for an exit was not marked "Not an Exit" or similar designation, or be identified by a sign indicating its actual use (e.g. closet):  A.  On or about November 19, 2015, near Rest Rooms:  A side-hinged door that could be mistaken for an exit was not identified with its actual use or a sign indicating "Not an Exit."  The door was locked with a deadbolt during building occupancy.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.147 C01

Serious Gravity 5 1 instance 1 exposed
Issued
Dec 1, 2015
Abate by
May 31, 2016
Penalty
Initial $3,500 · Current $1,750 Reduced
29 CFR 1910.147(c)(1): The employer did not establish a program consisting of an energy control procedure, employee training and periodic inspections to ensure that before any employee performed any servicing or maintenance on a machine or equipment where the unexpected energizing, startup or release of stored energy could occur and cause injury, the machine or equipment shall be isolated from the energy source and rendered inoperative:  A.  On or about November 19, 2015, Production Shop:  The employer had not developed a lockout/tagout program to address the hazards of unexpected startup of multiple-energy source equipment during service or maintenance.
Recent events (2)
  • — I (S) $1750
  • — Z (S) $3500

1910.212 A01

Serious Gravity 5 1 instance 29 exposed
Issued
Dec 1, 2015
Abate by
Jan 20, 2016
Penalty
Initial $3,500 · Current $1,750 Reduced
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:  A,  On or about November 19, 2015, Production Shop:  Nakamura Tome Methods Slant CNC Lathe, L25 had an unguarded rotating spindle on the left side of the equipment, adjacent to a walkway, 44 inches from the ground.
Recent events (2)
  • — I (S) $1750
  • — Z (S) $3500

1910.212 A03 II

Serious Gravity 5 2 instances 2 exposed
Issued
Dec 1, 2015
Abate by
Mar 3, 2016
Penalty
Initial $3,500 · Current $1,750 Reduced
29 CFR 1910.212(a)(3)(ii): Point(s) of operation of machinery were not guarded to prevent employee(s) from having any part of their body in the danger zone(s) during operating cycle(s):   A.  On or about November 19, 2015, Production Shop:  In the following instances, equipment was not provided with interlocked guards to ensure employees could not contact the points of operation during the operating cycle.  Spindles continued to rotate while the guard doors were opened:  1.  Nakamura Tome CNC Lathe #L25. 2.  Hitachi Seiki CNC Lathe 4NE-600. 3.  Hardinge Super Precision Lathe.
Recent events (2)
  • — I (S) $1750
  • — Z (S) $3500

1910.242 B

Serious Gravity 5 2 instances 2 exposed
Issued
Dec 1, 2015
Abate by
Jan 20, 2016
Penalty
Initial $2,800 · Current $1,400 Reduced
29 CFR 1910.242(b): Compressed air used for cleaning purposes was not reduced to less than 30 p.s.i.:  A.  On or about November 19, 2015, Production Shop:  In the following locations, compressed air used for cleaning was not reduced to below 30 p.s.i.:  1.  Matsuura CNC Machining Center MC600VF  2.  Wasino CNC Lathe XL3-J3
Recent events (2)
  • — I (S) $1400
  • — Z (S) $2800

1910.303 F02

Serious Gravity 5 2 instances 1 exposed
Issued
Dec 1, 2015
Abate by
Jan 20, 2016
Penalty
Initial $3,500 · Current $1,750 Reduced
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:  A.  On or about November 19, 2015, Inactive Tool Room:  Electrical panels were not clearly marked to indicate the specific purpose of each circuit.   1.   The main service panel had an illegible circuit directory.  2.  The subpanel had a circuit directory that had not been filled in.
Recent events (2)
  • — I (S) $1750
  • — Z (S) $3500

1910.305 B01 II

Serious Gravity 5 4 instances 29 exposed
Issued
Dec 1, 2015
Abate by
Jan 20, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:  A.  On or about November 19, 2015, Break Room: Electrical outlets on the west wall of the break room had unused openings which had not been covered:   1  A wall mounted 4-outlet receptacle box had two knockouts missing at the top of the box.  The receptacles powered an Emerson microwave oven, General Electric microwave oven and Hamilton Beach toaster oven.  2.  A wall mounted 4-outlet receptacle box had one knockout missing at the right side of the box.  The receptacles powered the Mr. Coffee 10-cup coffee maker, a Mr. Coffee 4-cup coffee maker and a Hamilton Beach electric teapot.   B.  On or about November 19, 2015, Inactive Tool Room:  1.  The 240V main electrical panel was missing breakers or blanks on eighteen openings.  2.  The 120V electrical panel was missing breakers or blanks on ten openings.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 D02

Serious Gravity 5 1 instance 1 exposed
Issued
Dec 1, 2015
Abate by
Jan 20, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(d)(2): Panelboards were not mounted in cabinets, cutout boxes, or enclosures designed for the purpose and/or were not dead front:   A.  On or about November 19, 2015, Inactive Tool Room:  The door and dead front of the 240V main electrical panel were not fully attached.  When the unlocked door opened, the dead front pulled away from the right side of the panel exposing all of the energized parts inside.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.304 G05

Serious Gravity 5 2 instances 29 exposed
Issued
Dec 1, 2015
Abate by
Jan 20, 2016
Penalty
Initial $4,200 · Current $2,100 Reduced
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:  A.  On or about November 19, 2015, Break Room:  Current was detected in the metal parts of the following equipment:   1.  The Mr. Coffee 10-cup coffee maker did not have a grounding pin.  2.  The metal-encased Emerson microwave had energy transmitted to its metal parts.
Recent events (2)
  • — I (S) $2100
  • — Z (S) $4200

View Polar Corporation's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341056596.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.