OSHA Inspection: MEISNER ELECTRIC INC. OF FLORIDA

Unprogrammed Related inspection · Safety discipline

On , OSHA opened an unprogrammed Related safety inspection of MEISNER ELECTRIC INC. OF FLORIDA in 650 PIONEER ROAD, JUPITER, FL 33458 (NAICS 238210). OSHA activity number 341061182.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Meisner Electric INC. of Florida — free Get an email when a new federal OSHA severe-injury report for Meisner Electric INC. of Florida is published. One employer, no account, unsubscribe in one click.
Site address
650 PIONEER ROAD
City
JUPITER
State
FL
ZIP
33458
Mailing
220 NE 1ST STREET, DELRAY BEACH, FL 33444
Inspection type
Unprogrammed Related (G)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
10
Ownership type
A

3 citations on file for this inspection.

1926.152 D02

Serious Gravity 5 1 instance 1 exposed
Issued
Dec 18, 2015
Penalty
Initial $1,600 · Current $960 Reduced
29 CFR 1926.152(d)(2): A portable fire extinguisher having a rating of not less than 20-B units was not located between 25 feet and 75 feet from flammable liquid storage area(s) located outside:  On or about November 17, 2015, at the above addressed site, an employee was exposed to burns when working near a 500 gallon Diesel tank that did not have a fire extinguisher located not less than 25 feet, or more than 75 feet from the tank.
Recent events (2)
  • — I (S) $960
  • — Z (S) $1600

1926.152 E04

Serious Gravity 5 1 instance 1 exposed
Issued
Dec 18, 2015
Penalty
Initial $1,600 · Current $960 Reduced
29 CFR 1926.152(e)(4): Units dispensing flammable or combustible liquids were not protected against collision damage:  On or about November 17, 2015, at the above addressed site, an employee was exposed to burns when working near a 500 gallon Diesel tank that was not protected against collision damage from construction equipment being operated adjacent to that tank.
Recent events (2)
  • — I (S) $960
  • — Z (S) $1600

1910.1200 F10

Other-than-serious 1 instance 1 exposed
Issued
Dec 18, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.1200(f)(10): The employer did not ensure that workplace labels or other forms of warnings were prominently displayed on the container or readily available in the work area throughout each work shift  On or about November 17, 2015, at the above addressed site, an employee was exposed to burns when working near a 500 gallon Diesel tank that was not labeled to identify the contents held within it.