Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: GOLD MEDAL ENVIRONMENTAL OF DE, LLC

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of GOLD MEDAL ENVIRONMENTAL OF DE, LLC in 1000 S. HEALD STREET, WILMINGTON, DE 19801 (NAICS 423930). OSHA activity number 341063097.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Gold Medal Environmental of DE, LLC — free Get an email when a new federal OSHA severe-injury report for Gold Medal Environmental of DE, LLC is published. One employer, no account, unsubscribe in one click.
Site address
1000 S. HEALD STREET
City
WILMINGTON
State
DE
ZIP
19801
Mailing
1000 SOUTH HEALD STREET, WILMINGTON, DE 19801
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
423930
Employees
25
Ownership type
A

2 citations on file for this inspection.

1910.304 E01 I

Serious Gravity 5 1 instance 2 exposed
Issued
Apr 25, 2016
Abate by
May 5, 2016
Penalty
Initial $3,060 · Current $2,295 Reduced
29 CFR 1910.304(e)(1)(i): Means was not provided to disconnect all conductors in a building or other structure from the service-entrance conductors. The service disconnecting means was not plainly indicated and was not readily accessible nearest the point of entrance of the service-entrance conductors:   a) 1000 S. Heald Street, Wilmington, DE (Maintenance Shop), On or about November 17, 2015, the employer failed to provide means to disconnect all conductors and they were not plainly indicated, exposing employees to electrical hazards.
Recent events (2)
  • — I (S) $2295
  • — Z (S) $3060

1910.305 D02

Serious Gravity 5 1 instance 2 exposed
Issued
Apr 25, 2016
Abate by
May 5, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(d)(2): Panelboards were not mounted in cabinets, cutout boxes, or enclosures designed for the purpose and/or were not dead front:    a) 1000 S. Heald Street, Wilmington, DE (Maintenance Shop), On or about November, 17, 2015, the panelboards were not designed for the purpose of dead front, the doors on electrical panels were damaged and did not close, exposing employees to electrical hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341063097.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.