FIFE, WA —
OSHA Inspection: EMERALD QUEEN CASINO & HOTEL
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of EMERALD QUEEN CASINO & HOTEL in 5700 PACIFIC HIGHWAY EAST, FIFE, WA 98424 (NAICS 721120). OSHA activity number 341089290.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- EMERALD QUEEN CASINO & HOTEL
- Site address
- 5700 PACIFIC HIGHWAY EAST
- City
- FIFE
- State
- WA
- ZIP
- 98424
- Mailing
- 5700 PACIFIC HIGHWAY EAST, FIFE, WA 98424
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 721120
- Employees
- 1000
- Ownership type
- A
Citations
7 citations on file for this inspection.
1910.303 B02
- Issued
- Dec 29, 2015
- Abate by
- Feb 3, 2016
- Penalty
- Initial $2,550 · Current $1,275 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) South Garage Shop: A relocatable power tap (surge protector) was plugged into an extension cord which powered Milwaukee battery chargers and a florescent shop light. The UL listing states that relocatable power taps are designed to be plugged into an outlet, and not daisy chained and plugged into other relocatable power taps or extension cords. This exposes employees to possible electrical fire hazards. b) Outside Maintenance Shop: A relocatable power tap (surge protector) was plugged into another relocatable power tap (surge protector) which powered a Haier refrigerator and DeWalt battery chargers. The UL listing states that relocatable power taps are designed to be plugged into an outlet, and not daisy chained and plugged into other relocatable power taps or extension cords. The UL listing states that relocatable power taps are designed for low amperage computer and audiovisual types of equipment, and not appliances. This exposes employees to possible electrical fire hazards. c) Construction/Design cubicle in Executive Suite: A Fellows surge protector was plugged into another Fellows surge protector which was powering a laptop. The UL listing states that relocatable power taps are designed to be plugged into an outlet, and not daisy chained and plugged into other relocatable power taps or extension cords. This exposes employees to possible electrical fire hazards. d) Southwest Office in Finance: A white surge protector was plugged into a yellow surge protector. A Holmes heater was plugged into a surge protector. The UL listing states that relocatable power taps are designed to be plugged into an outlet, and not daisy chained and plugged into other relocatable power taps or extension cords. The UL listing states that relocatable power taps are designed for low amperage computer and audiovisual types of equipment, and not appliances. This exposes employees to possible electrical fire hazards. e) Income Audit cubicle 3 down from the window: A white surge protector was plugged into another white surge protector. The UL listing states that relocatable power taps are designed to be plugged into an outlet, and not daisy chained and plugged into other relocatable power taps or extension cords. This exposes employees to possible electrical fire hazards. f) Tribal Lottery Systems Room 114: A refrigerator and West Bend microwave were plugged into a relocatable power tap. The UL listing states that relocatable power taps are designed for low amperage computer and audiovisual types of equipment, and not appliances. This exposes employees to possible electrical fire hazards. g) Tribal Lottery Systems Room 114: Two relocatable power taps were plugged into an extension cord. One relocatable power tap was plugged into another relocatable power tap. The relocatable power taps were powering a Weller brand soldering station, Motorola battery chargers and DeWalt battery charger. The UL listing states that relocatable power taps are designed to be plugged into an outlet, and not daisy chained and plugged into other relocatable power taps or extension cords. This exposes employees to possible electrical fire hazards.
Recent events (2)
- — I (S) $1275
- — Z (S) $2550
1910.37 B02
- Issued
- Dec 29, 2015
- Abate by
- Feb 3, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit": a) South Garage Shop/ Paint Shop: Exit discharge doors did not have exit signs. b) Electrician/Carpenter Shop: Exit discharge doors did not have exit signs.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.159 C10
- Issued
- Dec 29, 2015
- Abate by
- Feb 3, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.159(c)(10): The minimum vertical clearance of 18 inches between automatic sprinkler systems sprinklers and the material below was not maintained: a) Employee restaurant locker room: Hats, scarves, gloves and coats were stored on top of lockers 11 inches from the sprinkler head.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.213 S06
- Issued
- Dec 29, 2015
- Abate by
- Feb 3, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.213(s)(6): Cleanliness around working machinery was not maintained to prevent fire hazards and ensure the effective functioning of guards: a) Electrician/ Carpenter Shop: Sawdust was located around and underneath the DeWalt miter saw and Porter Cable table saw.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.303 G01 II
- Issued
- Dec 29, 2015
- Abate by
- Feb 3, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: a) South Garage Shop: Panel S1A, cases of water and sheetrock were stored beneath the breaker panel. Panel S1D, Deicer and boots were stored underneath the breaker panel. CORRECTED DURING INSPECTION b) Electrician/ Carpenter Shop: Panel N1A, buckets of poly lime and metal electrical parts were stored underneath the breaker panel. Panel N1D, a metal step ladder and spools of wire were stored underneath the breaker panel. c) Ballroom Dishwashing Area: Boxes of gloves and a trash can were stored underneath the breaker panels. CORRECTED DURING INSPECTION d) Paradise Deli Kitchen: Bins and pizza boxes were stored underneath the breaker panel. e) Tatoosh Restaurant Electrical Room: An oil disposal system and caution/slippery floor signs were stored underneath a breaker panel.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.305 B01 II
- Issued
- Dec 29, 2015
- Abate by
- Feb 3, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: a) Outside Shop/ Grounds keeping Area: The electrical panel was missing a knockout.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.334 A02 II
- Issued
- Dec 29, 2015
- Abate by
- Feb 3, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.334(a)(2)(ii): There was a defect or evidence of damage that could have exposes an employee to injury and the defective or damaged item was not removed from service: a) Tatoosh Kitchen: The Panasonic microwave's power cord was pulled from its strain relief.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Emerald Queen Casino & Hotel
View Emerald Queen Casino & Hotel's full OSHA safety record →
More inspections in this industry (NAICS 721120)
More inspections in WA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341089290.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.