Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,645Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: AIR FORCE

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of AIR FORCE in 354TH CIVIL ENGINEERING SQUADRON BUILDING 2350, EIELSON AFB, AK 99702 (NAICS 561210). OSHA activity number 341104040.

Watch AIR Force — free Get an email when a new federal OSHA severe-injury report for AIR Force is published. One employer, no account, unsubscribe in one click.
Establishment
AIR FORCE
Site address
354TH CIVIL ENGINEERING SQUADRON BUILDING 2350
City
EIELSON AFB
State
AK
ZIP
99702
Mailing
354 BROADWAY AVENUE SUITE 14A, EIELSON AFB, AK 99702
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
561210
Employees
100
Ownership type
D

5 citations on file for this inspection.

1910.23 D01 I

Serious Gravity 1 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.23(d)(1)(i): Flight(s) of stairs with four or more risers, less than 44 inches wide and having both sides enclosed, were not equipped with at least one standard handrail.  Building 2350, stairwell leading to storage area above alarm shop; on or about 02 December 2015 and times prior thereto; a stairway measuring 42 inches in width with ten vertical risers was not equipped with a standard handrail on either side. This condition exposed employees to a fall hazard.
Recent events (1)
  • — Z (S) $0

1910.23 D01 IV

Serious Gravity 5 1 instance 10 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.23(d)(1)(iv): Flights of stairs with 4 or more risers, more than 44 inches wide but less than 88 inches wide, were not equipped with on standard handrail on each enclosed side.    Building 2350, entryway; on or about 02 December 2015 and times prior thereto; a stairway measuring 82.5 inches in width with seven vertical risers was not equipped with a standard handrail on either side. This condition exposed employees to a fall hazard.
Recent events (1)
  • — Z (S) $0

1910.37 A04

Serious Gravity 1 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.37(a)(4): Safeguard(s) designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting), were not in proper working order at all times.  Buildings 2350, structures shop; on or about 02 December 2015 and times prior; the employer did not ensure that emergency exits lights were in proper working order. This condition exposed employees to delays in exiting the building causing smoke inhalation and fire hazards.
Recent events (1)
  • — Z (S) $0

1910.212 A01

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks.   Building 2350, machine shop; on or about 02 December 2015 and times prior thereto; a Sound Bend Heavy Duty Gear Head Lathe, Model SB1050, Serial Number SB1050-0001; had the chuck guard removed. This condition exposed employees to a caught in hazard.
Recent events (1)
  • — Z (S) $0

1910.303 G01 II

Repeat Gravity 5 2 instances 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage.  Building 2350, Structures Shop, electrical room; on or about 02 December 2015 and times prior thereto; two instances were noted where electrical panels had items stored in front of the panel impeding immediate access.        a. A Kettler foldable ping pong table was stored in front of the main panel board.        b. Wooden planking was stored in front of the panel board adjacent to the dust collection blower fans.  This condition exposed employees to delays in de-energizing electrical equipment, electrical shock and electrical burn hazard.  The Air Force was previously cited for a violation of this occupational safety and health standard 29 CFR 1910.303(g)(1)(ii), which was contained in OSHA inspection number 111281, citation number 1, item number 3 and was affirmed as a final order on 06 March 2012, with respect to a workplace located at Eielson Air Force Base, 354th Civil Engineering Squadron, Structures Electrical room.
Recent events (1)
  • — Z (R) $0

View AIR FORCE's full OSHA safety record →