On , OSHA opened a planned safety inspection of AIR FORCE in 354TH CIVIL ENGINEERING SQUADRON PLUMBING SHOP, EIELSON AFB, AK 99702 (NAICS 238220). OSHA activity number 341104073.

Watch AIR Force — free Get an email when a new federal OSHA severe-injury report for AIR Force is published. One employer, no account, unsubscribe in one click.
Establishment
AIR FORCE
Site address
354TH CIVIL ENGINEERING SQUADRON PLUMBING SHOP
City
EIELSON AFB
State
AK
ZIP
99702
Mailing
354 BROADWAY AVENUE SUITE 14A, EIELSON AFB, AK 99702
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238220
Employees
100
Ownership type
D

6 citations on file for this inspection.

1910.37 A04

Serious Gravity 1 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.37(a)(4): Safeguard(s) designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting), were not in proper working order at all times.  Plumbing Shop, Bldg 2357; on or about 02 December 2015 and times prior; the employer did not ensure that emergency exits lights were in proper working order. This condition exposed employees to delays in exiting the building causing smoke inhalation and fire hazards.
Recent events (1)
  • — Z (S) $0

1910.303 G01 I B

Serious Gravity 1 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(g)(1)(i)(B): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the width of the working space in front of electrical equipment was less than the width of the equipment or 762 mm (30 inches), whichever was greater.    Plumbing Shop, Bldg 2357  On or about 1 December 2015 and times prior thereto, electrical was blocked with cleaning equipment. This condition exposed employees to an electrical shock and burn hazard.
Recent events (1)
  • — Z (S) $0

1910.304 A02

Serious Gravity 1 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.304(a)(2): Grounded conductors were attached to terminals or leads so as to reverse designated polarity.  Plumbing Shop, Bldg 2357;  On or about 2 December 2015 and times prior thereto, a 120 volt electrical outlet tested with reverse polarity.  This condition exposed employees to an electrical shock and burn hazard.
Recent events (1)
  • — Z (S) $0

1910.304 G05

Serious Gravity 5 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective.  Plumbing Shop, Bldg 2357,  On or about 2 December 2015 and times prior thereto, two refrigerators were connected to a 120 volt electrical outlet did not have a ground indication when tested.  This condition exposed employees to an electrical shock and burn hazard.
Recent events (1)
  • — Z (S) $0

1910.305 B01 II

Serious Gravity 1 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed.  Plumbing Shop, Bldg 1125, on or about 02 December 2015 and times prior thereto; A knockout plug was missing from a energized electrical outlet box. This condition exposed employees to electrical shock and electrical burn hazard.
Recent events (1)
  • — Z (S) $0

1960.8 A

Serious Gravity 5 2 instances 4 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1960.8(a): 29 CFR 1960.8(a):  The Agency head did not furnish employment and a place of employment to each employee that were free from recognized hazards that caused or were likely to cause death or serious physical harm.  Plumbing Shop, Bldg 1125; on or about 02 December 2015 and times prior thereto; warehouse storage racks were not secured to the wall or floor. This condition exposed employees to a struck by hazard.