HAMPTON, VA —
OSHA Inspection: DEPARTMENT OF VETERANS ADMINISTRATION MEDICAL CENTER
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of DEPARTMENT OF VETERANS ADMINISTRATION MEDICAL CENTER in 100 EMANCIPATION DRIVE, HAMPTON, VA 23667 (NAICS 622110). OSHA activity number 341104834.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- DEPARTMENT OF VETERANS ADMINISTRATION MEDICAL CENTER
- Site address
- 100 EMANCIPATION DRIVE
- City
- HAMPTON
- State
- VA
- ZIP
- 23667
- Mailing
- 100 EMANCIPATION DRIVE, HAMPTON, VA 23667
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 622110
- Employees
- 1700
- Ownership type
- D
Citations
9 citations on file for this inspection.
1910.23 C01
- Issued
- Jun 1, 2016
- Abate by
- Jun 27, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.23(c)(1): Open-sided floors and/or platforms four feet or more above adjacent floor or ground level were not guarded with standard railings (or equivalent): (a) Date of Violation: On or about 12-17-2015 and times prior thereto located at Hampton VA Medical Center, 100 Emancipation Drive Hampton, VA 23667, in the Carpentry Shop, employees were exposed to falls from a 9 feet, 5 inch wide open-sided, unguarded mezzanine work platform at a height of 15 feet, 4 inches above the ground level below. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employee(s) and their representatives were informed of this abatement.
Recent events (1)
- — Z (S) $0
1910.213 P04
- Issued
- Jun 1, 2016
- Abate by
- Jun 27, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.213(p)(4): Belt sanding machinery was not provided with a guard at each nip point where the sanding belt ran onto a pulley, to prevent the operator's hands or fingers from coming into contact with nip points: (a) Date of Violation: On or about 12-17-2015 and times prior thereto located at Hampton VA Medical Center, 100 Emancipation Drive Hampton, VA 23667, in the Carpentry Shop, employees were exposed to unguarded rotating parts at the sanding belt pulley which also had a smaller rotating sanding drum attachment mounted on top of the belt pulley which placed the point of operation directly above the unguarded rotating pulley and drum. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employee(s) and their representatives were informed of this abatement.
Recent events (1)
- — Z (S) $0
1910.215 A04
- Issued
- Jun 1, 2016
- Abate by
- Jun 27, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.215(a)(4): Work rests. On offhand grinding machines, work rests were not used to support the work. The work rests was not kept adjusted closely to the wheel with a maximum opening of one-eighth inch to prevent the work from being jammed between the wheel and the rest, which may cause wheel breakage. (a) Date of Violation: On or about 12-17-2015 and times prior thereto located at Hampton VA Medical Center, 100 Emancipation Drive Hampton, VA 23667, in the Mechanic Shop building 8, employees were exposed to a floor mounted pedestal grinder that contained a work rest with adjustment exceeding one-eighth inch. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employee(s) and their representatives were informed of this abatement.
Recent events (1)
- — Z (S) $0
1910.215 B09
- Issued
- Jun 1, 2016
- Abate by
- Jun 27, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.215(b)(9): The distance between the abrasive wheel periphery(s) and the adjustable tongue or the end of the safety guard peripheral member at the top exceeded one fourth inch. (a) Date of Violation: On or about 12-17-2015 and times prior thereto located at Hampton VA Medical Center, 100 Emancipation Drive Hampton, VA 23667, in the Mechanics Shop, employees were exposed to struck-by hazards resulting from the adjustable tongue missing from the pedestal grinder. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employee(s) and their representatives were informed of this abatement.
Recent events (1)
- — Z (S) $0
1910.305 G01 IV A
- Issued
- Jun 1, 2016
- Abate by
- Jun 27, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and cables were used as a substitute for fixed wiring of a structure: (a) Date of Violation: On or about 12-17-2015 and times prior thereto located at Hampton VA Medical Center, 100 Emancipation Drive Hampton, VA 23667, in the Carpentry Shop, employees were exposed to fire and electrical hazards from a temporary extension cord permanently affixed to the wall to provide a means of power supply to a panel saw. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employee(s) and their representatives were informed of this abatement.
Recent events (1)
- — Z (S) $0
1910.305 G01 IV C
- Issued
- Jun 1, 2016
- Abate by
- Jun 27, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(C): Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used: Where run through doorways, windows, or similar openings: (a) Date of Violation: On or about 12-17-2015 and times prior thereto located at Hampton VA Medical Center, 100 Emancipation Drive Hampton, VA 23667, in the Mechanic Shop, employees were exposed to fire and electrical hazards from a 50 foot extension cord that was run through a garage door opening whereas the garage door could continue to open and close down on the cord as it went out towards the outside gravel area. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employee(s) and their representatives were informed of this abatement.
Recent events (1)
- — Z (S) $0
1910.305 G02 III
- Issued
- Jun 1, 2016
- Abate by
- Jun 27, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: (a) Date of Violation: On or about 12-17-2015 and times prior thereto located at Hampton VA Medical Center, 100 Emancipation Drive Hampton, VA 23667, in the Carpentry Shop paint mixing room, employees were exposed to electrical hazards from an extension cord constructed with wiring and a metal wall-mounted style outlet box and the strain relief fitting was not connected to the outlet box therefore putting strain directly on the terminal screws internal of the box. Cord was used to supply power to a paint shaking machine. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employee(s) and their representatives were informed of this abatement.
Recent events (1)
- — Z (S) $0
1910.303 B02
- Issued
- Jun 1, 2016
- Abate by
- Jun 27, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: (a) Date of Violation: On or about 12-17-2015 and times prior thereto located at Hampton VA Medical Center, 100 Emancipation Drive Hampton, VA 23667, in the Warehouse Area, employees were exposed to electrical hazards from electrical power strips/surge protectors that were "daisy-chained" and plugged directly into one another to provide power to computerized bench-top equipment. The United States Department of Veterans Affairs was previously cited for a violation of this Occupational Safety and Health Standard 29 CFR 1910.303(b)(2), which was contained in OSHA inspection number 1074778, citation number 2, item number 2 and was affirmed as a final order on 08-08-15, with respect to a workplace located at U.S. Department of Veterans Affairs Fresno, CA 93703. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employee(s) and their representatives were informed of this abatement.
Recent events (1)
- — Z (R) $0
1910.305 B01 II
- Issued
- Jun 1, 2016
- Abate by
- Jun 27, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: (a) Date of Violation: On or about 12-17-2015 and times prior thereto located at Hampton VA Medical Center, 100 Emancipation Drive Hampton, VA 23667, employees were exposed to electrical hazards from unused openings located in electrical enclosures. Instance #1: Warehouse storage room. A blanked off junction box contained an unused opening whereas a "knockout" was missing exposing the internal electrical parts of the junction box. Instance #2: Mechanics Shop, An EATON Cutler-Hammer electrical disconnect panel contained an unused opening whereas a "knockout" was missing exposing the internal electrical parts of the panel. This panel displayed warnings of arc flash hazard. Instance #3: Carpentry Shop, A power receptacle located underneath the Delta Belt Sander contained an unused opening whereas a "knockout" was missing exposing the internal electrical parts of the receptacle box. The United States Department of Veterans Affairs was previously cited for a violation of this Occupational Safety and Health Standard 29 CFR 1910.303(b)(2), which was contained in OSHA inspection number 1074778, citation number 2, item number 3 and was affirmed as a final order on 08-08-15, with respect to a workplace located at U.S. Department of Veterans Affairs Fresno, CA 93703. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employee(s) and their representatives were informed of this abatement.
Recent events (1)
- — Z (R) $0
More inspections at Department of Veterans Administration Medical Center
View Department of Veterans Administration Medical Center's full OSHA safety record →
More inspections in this industry (NAICS 622110)
More inspections in VA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341104834.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.