Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: TRINITY FORGE, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of TRINITY FORGE, INC. in 947 TRINITY DRIVE, MANSFIELD, TX 76063 (NAICS 332111). OSHA activity number 341105237.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Trinity Forge, INC. — free Get an email when a new federal OSHA severe-injury report for Trinity Forge, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
TRINITY FORGE, INC.
Site address
947 TRINITY DRIVE
City
MANSFIELD
State
TX
ZIP
76063
Mailing
947 TRINITY DRIVE, MANSFIELD, TX 76063
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332111
Employees
104
Ownership type
A

5 citations on file for this inspection.

1910.333 A

Serious Gravity 5 1 instance 1 exposed
Issued
Feb 2, 2016
Abate by
Mar 2, 2016
Penalty
Initial $4,500 · Current $2,700 Reduced
29 CFR 1910.333(a): Safety-related work practices were not employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work was performed near or on equipment or circuits which were or could be energized:   At the facility job site, the employer did not ensure maintenance employees assigned to troubleshoot and repair the Induction Furnace, 480 Volt Service Disconnect #3 of 6, were provided with a safe method from either direct or indirect electrical contacts when working on or near energized 480 Volts 3 Phase electrical panels exposing employees to electrical shock and/or arc blast hazards.
Recent events (2)
  • — I (S) $2700
  • — Z (S) $4500

1910.333 A01

Serious Gravity 5 1 instance 1 exposed
Issued
Feb 2, 2016
Abate by
Mar 2, 2016
Penalty
Initial $4,050 · Current $2,430 Reduced
29 CFR 1910.333(a)(1): Live parts to which an employee may be exposed were not deenergized before the employee worked on or was near to them:  At the facility job site, the employer did not ensure the 480 Volt Service Disconnect #3 of 6 was completely deenergized prior to allowing employees to work on or near the energized 480 Volts 3 Phase electrical panels exposing employees to electrical shock and/or arc blast hazards.
Recent events (2)
  • — I (S) $2430
  • — Z (S) $4050

1910.333 B02 IV B

Serious Gravity 5 1 instance 1 exposed
Issued
Feb 2, 2016
Abate by
Mar 2, 2016
Penalty
Initial $4,050 · Current $2,430 Reduced
29 CFR 1910.333(b)(2)(iv)(B): Before circuits or equipment was worked as de-energized, a qualified person did not use test equipment to test the circuit elements and electrical parts of equipment to which employees would be exposed and did not verify that electrical power was de-energized:  At the facility job site, the employer did not ensure maintenance employees assigned to troubleshoot and repair the 480 Volt Service Disconnect #3 of 6 verified that the electrical disconnect was de-energized prior to allowing employees to work on or near the energized electrical panels exposing the employees to arc blast and/or electrical shock hazards.
Recent events (2)
  • — I (S) $2430
  • — Z (S) $4050

1910.335 A01

Serious Gravity 5 1 instance 1 exposed
Issued
Feb 2, 2016
Abate by
Mar 2, 2016
Penalty
Initial $4,050 · Current $2,430 Reduced
29 CFR 1910.335(a)(1): Employees working in areas where there were potential electrical hazards were not provided with, and/or did not use, electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed:  At the facility job site, the employer did not ensure maintenance employees assigned to troubleshoot and repair the 480 Volt Service Disconnect #3 of 6 used personal protective equipment associated to the hazards of working on or near energized 480 Volts 3 Phase electrical panels exposing employees to arc blast and/or electrical shock injuries.
Recent events (2)
  • — I (S) $2430
  • — Z (S) $4050

1910.335 A01 V

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 2, 2016
Abate by
Mar 2, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.335(a)(1)(v): Employees exposed to the danger of injury to the eyes or face from electric arcs or flashes or from flying objects resulting from electrical explosion did not wear protective equipment for the eyes or face:  At the facility job site, the employer did not ensure maintenance employees assigned to troubleshoot and repair the 480 Volt Service Disconnect #3 of 6 wore eye or face protective equipment associated to the hazards of working on or near energized 480 Volts 3 Phase electrical panels exposing employees to arc blast and/or electrical shock injuries.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View Trinity Forge, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341105237.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.