Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: WOOD SYSTEMS, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of WOOD SYSTEMS, INC. in 4615 S. 49TH WEST AVE., TULSA, OK 74107 (NAICS 321918). OSHA activity number 341130045.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Wood Systems, INC. — free Get an email when a new federal OSHA severe-injury report for Wood Systems, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
WOOD SYSTEMS, INC.
Site address
4615 S. 49TH WEST AVE.
City
TULSA
State
OK
ZIP
74107
Mailing
4615 S. 49TH WEST AVE., TULSA, OK 74107
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
321918
Employees
60
Ownership type
A

5 citations on file for this inspection.

1910.106 E06 II

Other-than-serious 1 instance 5 exposed
Issued
Mar 2, 2016
Abate by
Mar 8, 2016
Penalty
Initial $1,785 · Current $1,050 Reduced
29 CFR 1910.106(e)(6)(ii):  Class I flammable liquid(s) were dispensed into containers, vehicles, and equipment without electrically interconnecting the nozzle and the container, vehicles, or equipment:       On or about December 15, 2015, and at times prior thereto, in the paint area lacquer thinner having flash point of 2 degrees F was dispensed into a smaller container without being effectively grounded and bonded to electrically interconnect the containers, exposing employees to a fire hazard.
Recent events (2)
  • — I (O) $1050
  • — Z (S) $1785

1910.107 C06

Other-than-serious 1 instance 2 exposed
Issued
Mar 2, 2016
Abate by
Mar 24, 2016
Penalty
Initial $1,785 · Current $1,050 Reduced
29 CFR 1910.107(c)(6): Electrical wiring and equipment not subject to deposits of combustible residues but located in a spraying area as herein defined were not explosion-proof type approved for Class I, group D locations and did not otherwise conform to the provisions of subpart S of this part, for Class I, Division 1, Hazardous Locations:         On or about December 15, 2015, and at times prior thereto, in the spray booth area electrical outlets and switches were observed within 5 feet of the opening of an open face spray booth were not the type approved for Class I, Division 1, hazardous locations.  Employees were exposed to fire hazards.
Recent events (2)
  • — I (O) $1050
  • — Z (S) $1785

1910.147 C04 I

Other-than-serious 2 instances 7 exposed
Issued
Mar 2, 2016
Abate by
Mar 24, 2016
Penalty
Initial $2,975 · Current $1,700 Reduced
29 CFR 1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section:       On or about December 15, 2015, and at times prior thereto, at the establishment the employer did not effectively develop and document proper step-by-step lock-out/tag-out procedures for the control of potentially hazardous energy of specific equipment when employees were engaged in maintenance operation.  Employees were exposed to unexpected release of energy hazards.
Recent events (2)
  • — I (O) $1700
  • — Z (S) $2975

1910.147 C06 I

Other-than-serious 1 instance 7 exposed
Issued
Mar 2, 2016
Abate by
Mar 24, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(6)(i): The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed:       On or about December 15, 2015, and at times prior thereto, at the establishment the employer had employees performing maintenance operations that require lock-out/tag-out equipment. The employer did not conduct periodic inspection of the procedures at least annually.   Employees were exposed to unexpected release of energy hazards.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.22 A01

Other-than-serious 1 instance 1 exposed
Issued
Mar 2, 2016
Abate by
Mar 8, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.22(a)(1): All places of employment, passageways, storerooms or service rooms were not kept clean and orderly or in a sanitary condition:    On or about December 15, 2015, and at times prior thereto, in the KOMO router area wood dust was found accumulated on floors and ledges of building.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Wood Systems, INC.'s full OSHA safety record →