Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: CONTROL ELECTRICAL CONTRACTING CORP.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of CONTROL ELECTRICAL CONTRACTING CORP. in 2 TELEPORT DRIVE, STATEN ISLAND, NY 10311 (NAICS 238210). OSHA activity number 341159424.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Control Electrical Contracting Corp. — free Get an email when a new federal OSHA severe-injury report for Control Electrical Contracting Corp. is published. One employer, no account, unsubscribe in one click.
Site address
2 TELEPORT DRIVE
City
STATEN ISLAND
State
NY
ZIP
10311
Mailing
85 THOMPKINS STREET, STATEN ISLAND, NY 10304
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
30
Ownership type
A

4 citations on file for this inspection.

1926.95 A

Serious Gravity 10 1 instance 1 exposed
Issued
Jun 29, 2016
Penalty
Initial $4,900 · Current $4,778 Reduced
29 CFR 1926.95(a): Protective equipment, including personal protective equipment for eyes, face, head, and extremities, protective clothing, respiratory devices, and protective shields and barriers, were not provided:    a) 2 Teleport Drive, Staten Island, NY 10311. Employee was exposed to electrical flash hazards to his eyes, face, and extremities when the employer did not provide the appropriate PPE for the employee while installing a relocated Vacu-Break, Clampmatic Action Fusible switch on an energized busway.     Incident occurred on or about 01/05/2016.
Recent events (3)
  • — R (S) $4777.5
  • — C (S) $4900
  • — Z (S) $4900

1926.416 A01

Serious Gravity 10 1 instance 1 exposed
Issued
Jun 29, 2016
Penalty
Initial $4,900 · Current $4,778 Reduced
29 CFR 1926.416(a)(1): Employees were permitted to work in proximity to electric power circuits and were not protected against electric shock by de-energizing and grounding the circuits or effectively guarding the circuits by insulation or other means:      a) 2 Teleport Drive, Staten Island, NY 10311. Employee was exposed to electrical shock and flash hazards when employer permitted him to work on an energized power circuit when it was not de-energized, grounded and or effectively guarded by insulation or other means.    Incident occurred on or about 01/05/2016.
Recent events (3)
  • — R (S) $4777.5
  • — C (S) $4900
  • — Z (S) $4900

1926.416 A03

Serious Gravity 10 1 instance 1 exposed
Issued
Jun 29, 2016
Penalty
Initial $0 · Current $0
29 CFR 1926.416(a)(3): Before work began, the employer did not ascertain by inquiry, direct observation, or by instruments, whether any part of an energized electric power circuit, exposed or concealed, was so located that the performance of the work could bring a person, tool, or machine into physical or electrical contact with an energized electric power circuit:  a) 2 Teleport Drive, Staten Island, NY 10311. Employee was exposed to shock and flash hazards when the employer did not verify correct switch was being installed resulting in cross phasing of polarity.  Incident occurred on or about 01/05/2016.
Recent events (3)
  • — R (S) $0
  • — C (S) $0
  • — Z (S) $0

1926.404 A02

Serious Gravity 10 1 instance 1 exposed
Issued
Jun 29, 2016
Penalty
Initial $4,900 · Current $0 Reduced
29 CFR 1926.404(a)(2): A grounded conductor was attached to a terminal or lead so as to reverse designated polarity:    a) 2 Teleport Drive, Staten Island, NY 10311. Employee was exposed to electrical flash when working on a 277/480 volt energized bus duct while installing an incorrectly wired Vacu-Break, Clampmatic Action Fusible Switch when one of the phases was mixed up with the Neutral.    Incident occurred on or about 01/05/2016.
Recent events (3)
  • — R (S) $0
  • — C (S) $4900
  • — Z (S) $4900

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341159424.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.