MOUNT VERNON, OH ·
OSHA Inspection: BUCKINGHAM ELECTRIC
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of BUCKINGHAM ELECTRIC in 35 BLACK JACK RD, MOUNT VERNON, OH 43050 (NAICS 238210). OSHA activity number 341202711.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- BUCKINGHAM ELECTRIC
- Site address
- 35 BLACK JACK RD
- City
- MOUNT VERNON
- State
- OH
- ZIP
- 43050
- Mailing
- 9572 HAZEL DELL ROAD, HOWARD, OH 43028
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 3
- Ownership type
- Private (A)
Citations
2 citations on file for this inspection.
1926.416 A01
- Issued
- Jun 6, 2016
- Abate by
- Jun 16, 2016
- Penalty
- Initial $2,800 · Current $1,960 Reduced
General-duty citation text
29 CFR 1926.416(a)(1): No employer shall permit an employee to work in such proximity to any part of an electric power circuit that the employee could contact the electric power circuit in the course of work, unless the employee is protected against electric shock by deenergizing the circuit and grounding it or by guarding it effectively by insulation or other means. a. On or about January 18, 2016, at 35 Blackjack Road an employee did not de-energize the Cutler Hammer 800 Amp switchboard prior to removing existing breakers and installing new breakers and buss mounting brackets on a 1200 volt panel.
Recent events (2)
- · I (S) $1960
- · Z (S) $2800
1926.416 A03
- Issued
- Jun 6, 2016
- Abate by
- Jun 16, 2016
- Penalty
- Initial $2,800 · Current $1,960 Reduced
General-duty citation text
29 CFR 1926.416(a)(3): Before work is begun the employer shall ascertain by inquiry or direct observation, or by instruments, whether any part of an energized electric power circuit, exposed or concealed, is so located that the performance of the work may bring any person, tool, or machine into physical or electrical contact with the electric power circuit. The employer shall post and maintain proper warning signs where such a circuit exists. The employer shall advise employees of the location of such lines, the hazards involved, and the protective measures to be taken. a. On or about January 18, 2016, at 35 Blackjack Road an employee used a non-insulated nut driver when replacing circuit breakers on the Cutler Hammer 800 amp switchgear an arc flash followed causing first and second degree burns to the employee. b. On or about January 18, 2016, at 35 Blackjack Road an employee was within the arc flash boundary assisting another employee replacing circuit breakers on the Cutler Hammer 800 amp switchgear an arch flash occurred causing first degree burns to the employee.
Recent events (2)
- · I (S) $1960
- · Z (S) $2800
More inspections in this industry (NAICS 238210)
More inspections in OH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 341202711.