CHEYENNE WELLS, CO —
OSHA Inspection: CARGILL INC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of CARGILL INC in 934 S 4TH ST W, CHEYENNE WELLS, CO 80810 (NAICS 424510). OSHA activity number 341203644.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CARGILL INC
- Site address
- 934 S 4TH ST W
- City
- CHEYENNE WELLS
- State
- CO
- ZIP
- 80810
- Mailing
- PO BOX 908, CHEYENNE WELLS, CO 80810
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 424510
- Employees
- 8
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.27 F
- Issued
- Mar 29, 2016
- Abate by
- Apr 29, 2016
- Penalty
- Initial $5,500 · Current $2,500 Reduced
General-duty citation text
29 CFR 1910.27(f): Ladders were not maintained in a safe condition: a) Bin C5: On or about January 21, 2016 and at times prior, workers were exposed to emergency egress hazards where the self-evacuation ladder had severely damaged rungs and side rails.
Recent events (2)
- — I (O) $2500
- — Z (S) $5500
1910.303 G01 VII B
- Issued
- Mar 29, 2016
- Abate by
- Apr 8, 2016
- Penalty
- Initial $7,000 · Current $7,000
General-duty citation text
29 CFR 1910.303(g)(1)(vii)(B): Outdoor electric equipment was not installed in suitable enclosures and/or was not protected from accidental contact by unauthorized personnel, or by vehicular traffic, or by accidental spillage or leakage from piping systems: a) Site C: On or about January 21, 2016 and at times prior, panels on bins c7 and c8, and of similar design, were not fitted with suitable latch mechanisms or other means to prevent accidental contact. Abatement Note: Abatement certification and documentation are required for this item (see enclosed Certification of Corrective Action Worksheet).
Recent events (2)
- — I (O) $7000
- — Z (S) $7000
1910.305 A01 I
- Issued
- Mar 29, 2016
- Abate by
- Apr 8, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(a)(1)(i): Metal raceways, cable armor, and other metal enclosures for conductors were not metallically joined together into a continuous electric conductor: a) Bin C12: On or about January 21, 2016 and at times prior, workers were exposed to electrical shock hazards caused by a disconnected conduit fitting that was straining two insulated conductors. b) Bin C7: On or about January 21, 2016 and at times prior, workers were exposed to electrical shock hazards at a blower where the j-box was disconnected from the motor. Abatement Note: Abatement certification and documentation are required for this item (see enclosed Certification of Corrective Action Worksheet).
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 J01 I
- Issued
- Mar 29, 2016
- Abate by
- Apr 8, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(j)(1)(i): Fixtures, lampholders, lamps, rosettes, and receptacles located within 8 feet of the floor had live parts exposed to employee contact: a) Old scale house basement: On or about January 21, 2016 and at times prior, workers were exposed to an electrical shock hazard where the connecting wires of a broken light bulb were protruding from an energized incandescent rosette-type fixture. Abatement Note: Abatement certification and documentation are required for this item (see enclosed Certification of Corrective Action Worksheet).
Recent events (2)
- — I (O) $0
- — Z (S) $0
1910.303 B07 IV
- Issued
- Mar 29, 2016
- Abate by
- Apr 8, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(7)(iv): There were damaged parts that adversely affected safe operation or mechanical strength of the equipment, such as parts that are broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating: a) Bin C8: On or about January 21, 2016 and at times prior, workers were exposed to electrical shock hazards at an electrical outlet with damage that included broken insulating material and a cord ground lug broken off in the receptacle. b) Bin C12: On or about January 21, 2016 and at times prior, workers were exposed to electrical shock hazards caused by a disconnected conduit fitting that was straining two insulated conductors. c) Bin C7: On or about January 21, 2016 and at times prior, workers were exposed to electrical shock hazards at a blower where the j-box was disconnected from the motor. Abatement Note: Abatement certification and documentation are required for this item (see enclosed Certification of Corrective Action Worksheet).
Recent events (2)
- — I (O) $0
- — Z (S) $0
More inspections at Cargill INC
View Cargill INC's full OSHA safety record →
More inspections in this industry (NAICS 424510)
More inspections in CO
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341203644.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.