OSHA Inspection: CARGILL INC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of CARGILL INC in 934 S 4TH ST W, CHEYENNE WELLS, CO 80810 (NAICS 424510). OSHA activity number 341203644.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Cargill INC — free Get an email when a new federal OSHA severe-injury report for Cargill INC is published. One employer, no account, unsubscribe in one click.
Establishment
CARGILL INC
Site address
934 S 4TH ST W
City
CHEYENNE WELLS
State
CO
ZIP
80810
Mailing
PO BOX 908, CHEYENNE WELLS, CO 80810
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
424510
Employees
8
Ownership type
A

5 citations on file for this inspection.

1910.27 F

Other-than-serious 1 instance 5 exposed
Issued
Mar 29, 2016
Abate by
Apr 29, 2016
Penalty
Initial $5,500 · Current $2,500 Reduced
29 CFR 1910.27(f):     Ladders were not maintained in a safe condition:    a) Bin C5: On or about January 21, 2016 and at times prior, workers were exposed to emergency egress hazards where the self-evacuation ladder had severely damaged rungs and side rails.
Recent events (2)
  • — I (O) $2500
  • — Z (S) $5500

1910.303 G01 VII B

Other-than-serious 1 instance 5 exposed
Issued
Mar 29, 2016
Abate by
Apr 8, 2016
Penalty
Initial $7,000 · Current $7,000
29 CFR 1910.303(g)(1)(vii)(B): Outdoor electric equipment was not installed in suitable enclosures and/or was not protected from accidental contact by unauthorized personnel, or by vehicular traffic, or by accidental spillage or leakage from piping systems:    a) Site C: On or about January 21, 2016 and at times prior, panels on bins c7 and c8, and of similar design, were not fitted with suitable latch mechanisms or other means to prevent accidental contact.      Abatement Note: Abatement certification and documentation are required for this item (see enclosed Certification of Corrective Action Worksheet).
Recent events (2)
  • — I (O) $7000
  • — Z (S) $7000

1910.305 A01 I

Deleted Serious Gravity 10 1 instance 5 exposed
Issued
Mar 29, 2016
Abate by
Apr 8, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(a)(1)(i): Metal raceways, cable armor, and other metal enclosures for conductors were not metallically joined together into a continuous electric conductor:  a) Bin C12: On or about January 21, 2016 and at times prior, workers were exposed to electrical shock hazards caused by a disconnected conduit fitting that was straining two insulated conductors.  b) Bin C7: On or about January 21, 2016 and at times prior, workers were exposed to electrical shock hazards at a blower where the j-box was disconnected from the motor.    Abatement Note: Abatement certification and documentation are required for this item (see enclosed Certification of Corrective Action Worksheet).
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 J01 I

Other-than-serious 1 instance 3 exposed
Issued
Mar 29, 2016
Abate by
Apr 8, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(j)(1)(i): Fixtures, lampholders, lamps, rosettes, and receptacles located within 8 feet of the floor had live parts exposed to employee contact:    a) Old scale house basement: On or about January 21, 2016 and at times prior, workers were exposed to an electrical shock hazard where the connecting wires of a broken light bulb were protruding from an energized incandescent rosette-type fixture.      Abatement Note: Abatement certification and documentation are required for this item (see enclosed Certification of Corrective Action Worksheet).
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.303 B07 IV

Other-than-serious 1 instance 5 exposed
Issued
Mar 29, 2016
Abate by
Apr 8, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(7)(iv): There were damaged parts that adversely affected safe operation or mechanical strength of the equipment, such as parts that are broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating:    a) Bin C8: On or about January 21, 2016 and at times prior, workers were exposed to electrical shock hazards at an electrical outlet with damage that included broken insulating material and a cord ground lug broken off in the receptacle.     b) Bin C12: On or about January 21, 2016 and at times prior, workers were exposed to electrical shock hazards caused by a disconnected conduit fitting that was straining two insulated conductors.    c) Bin C7: On or about January 21, 2016 and at times prior, workers were exposed to electrical shock hazards at a blower where the j-box was disconnected from the motor.        Abatement Note: Abatement certification and documentation are required for this item (see enclosed Certification of Corrective Action Worksheet).
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

View Cargill INC's full OSHA safety record →