OSHA Inspection: LIMEY & COMPANY, INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of LIMEY & COMPANY, INC. in 2390 W 28TH ST, GREELEY, CO 80631 (NAICS 811111). OSHA activity number 341204188.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- LIMEY & COMPANY, INC.
- Site address
- 2390 W 28TH ST
- City
- GREELEY
- State
- CO
- ZIP
- 80631
- Mailing
- 2390 W 28TH ST, GREELEY, CO 80631
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 811111
- Employees
- 5
- Ownership type
- A
Citations
8 citations on file for this inspection.
1910.242 B
- Issued
- May 12, 2016
- Abate by
- Jun 8, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.242(b): Compressed air was used for cleaning purposes without being reduced to less than 30 p.s.i. and then only with effective chip guarding and personal protective equipment: (a) Limey & Company, Inc. at 2390 W. 28th St., Greeley, CO 80631: On and before January 25, 2016, the employer failed to ensure that compressed air used for cleaning purposes was reduced to less than 30 p.s.i. when dead-ended. Condition exposed employees utilizing the compressed air to physical hazards such as embolisms.
Recent events (1)
- · Z (S) $0
1910.303 B03
- Issued
- May 12, 2016
- Abate by
- Jun 8, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(3): Completed wiring installations where not free from short circuits and from grounds other than those required or permitted by this subpart. (a) Limey & Company, Inc., at 2390 W. 28th St., Greeley, CO 80631: On and before January 25, 2016, the employer failed to ensure that completed wiring installations were free from short circuits and grounding. Specifically, the car lift located in Bay # 8 trips the circuit breaker, which has to be reset, several times each day, indicating that there is a grounding or conductivity issue causing the current being transmitted through the car lifts wiring to surge above the circuit breakers maximum capacity. Condition exposed employees using the car lift to electrical and struck by hazards should the lift fail.
Recent events (1)
- · Z (S) $0
1910.303 B04
- Issued
- May 12, 2016
- Abate by
- Jun 8, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(4): Equipment intended to interrupt current at fault levels did not have an interrupting rating sufficient for the nominal circuit voltage and the current that was available at the line terminals of the equipment. (a) Limey & Company, Inc. at 2390 W. 28th Ave, Greeley, CO 80631: On and before January 25, 2016, the employer failed to ensure that equipment intended to interrupt current at fault levels had an interrupting rating sufficient for the nominal circuit voltage. Specifically, the circuit breaker intended to protect the bay# 8 lift tripped off line repeatedly and did not provide an interrupting rating sufficient to protect the equipment and personnel in the area. Condition exposed employees to electrical and fire hazards, and potentially struck by hazards should the lift fail, while using the lift in bay # 8.
Recent events (1)
- · Z (S) $0
1910.303 F01
- Issued
- May 12, 2016
- Abate by
- Jun 8, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(f)(1): Each disconnecting means required by this subpart for motors and appliances was not legibly marked to indicate its purpose. (a) Limey & Company, Inc. at 2390 W. 28th Ave., Greeley, CO 80631: On and before January 25, 2016, the employer failed to ensure that each disconnecting means required by this Subpart for motors and appliances was legibly marked to indicate its purpose. Circuit breakers at various breaker boxes controlling items such as the compressors, car lifts, and tire servicing equipment were not legibly marked for their purpose. Condition exposed employees attempting to secure equipment to struck by and electrical hazards.
Recent events (1)
- · Z (S) $0
1910.303 G01 I B
- Issued
- May 12, 2016
- Abate by
- Jun 8, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(i)(B): The width of working space in front of the electric equipment was not the width of the equipment or 762 mm (30 in.), whichever is greater. and permit a 90-degree opening of equipment doors or hinged panels. (a) Limey & Company, Inc., at 2390 W. 28th St. Greeley, CO 80631: On and before January 25, 2016, the employer failed to ensure that the width of working space in front of the electric equipment was the width of the equipment or 762 mm (30 in.). Specifically, the employer utilized the space in front of the electrical service panels in the lower storage room to store equipment, preventing the electrical panel doors from opening at 90 degrees.
Recent events (1)
- · Z (S) $0
1910.304 B03 I
- Issued
- May 12, 2016
- Abate by
- Jun 8, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(b)(3)(i): All 125-volt, single-phase, 15- and 20-ampere receptacles installed in bathrooms or on rooftops did not have ground-fault circuit-interrupter protection for personnel. (a) Limey & Company, Inc. at 2390 W. 28th St., Greeley, CO 80631: On and before January 25, 2016, the employer failed to ensure that all 125-volt, single-phase, 15- and 20-ampere receptacles installed in bathrooms had ground-fault circuit-interrupter (GFCI) protection for personnel. Condition exposed employees utilizing the bathrooms to potential electrical hazards.
Recent events (1)
- · Z (S) $0
1910.305 B02 I
- Issued
- May 12, 2016
- Abate by
- Jun 8, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each outlet box did not have a cover, faceplate, or fixture canopy. (a) Limey & Company, Inc. at 2390 W. 28th St., Greeley, CO 80631: On and before January 25, 2016, the employer failed to ensure that each outlet box had a cover, faceplate, or fixture canopy. Various electrical outlets were missing faceplates at several locations in the facility. Condition exposed employees to electrical hazards when attempting to use the outlets.
Recent events (1)
- · Z (S) $0
1910.305 G01 IV A
- Issued
- May 12, 2016
- Abate by
- Jun 8, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords were used as a substitute for the fixed wiring of a structure; (a) Limey & Company, Inc. 2390 W. 28th St., Greeley, CO 80631: On and before January 25, 2016, the employer failed to remove temporary wiring and replace with fixed wiring in the storage area adjacent to Bay #8, and in the storage area above the office. Condition exposed employees to potential electrical hazards.
Recent events (1)
- · Z (S) $0
More inspections at Limey & Company, INC.
View Limey & Company, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 811111)
More inspections in CO
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341204188.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.