Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: DEES ELECTRICAL, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of DEES ELECTRICAL, INC. in 978 WHITE CIR, HINESVILLE, GA 31313 (NAICS 238210). OSHA activity number 341206100.

Watch Dees Electrical, INC. — free Get an email when a new federal OSHA severe-injury report for Dees Electrical, INC. is published. One employer, no account, unsubscribe in one click.
Site address
978 WHITE CIR
City
HINESVILLE
State
GA
ZIP
31313
Mailing
P.O. BOX 101, HINESVILLE, GA 31310
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
25
Ownership type
A

2 citations on file for this inspection.

1926.403 B02

Serious Gravity 5 1 instance 3 exposed
Issued
Penalty
Initial $1700.00 · Current $1020.00 Reduced
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification:  a) Temporary Power at Jobsite- on or about January 26, 2016, Dees Electrical, Inc. installed an 4-inch X 4-inch electrical handy box that was designed to be secured and mounted.  The electrical handy box was lying on the ground and hard wired to the temporary power pole.  The electrical handy box was used by the siding sub-contractor employees to support electric power to hand tools, thereby exposing sub-contractor employees to shock and electrical hazards.
Recent events (2)
  • — I (S) $1020
  • — Z (S) $1700

1926.404 B01 II

Serious Gravity 5 1 instance 1 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1926.404(b)(1)(ii): On a construction site, where an assured equipment grounding program was not utilized, all 120-volt, single-phase, 15 and 20 ampere receptacle outlets which were not a part of the permanent wiring of the building or structure and which are in use by employees did not have approved ground fault circuit interrupters for personal protection.  a) Temporary Power Panel - On or about January 26, 2016, employees were allowed to use 4-inch X 4-inch electrical  handy box that was designed to be secured and mounted without the use of a Ground Fault Circuit Interrupters (GFCI), exposing employees to shock and electrocution hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341206100.