HINESVILLE, GA —
OSHA Inspection: DEES ELECTRICAL, INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of DEES ELECTRICAL, INC. in 978 WHITE CIR, HINESVILLE, GA 31313 (NAICS 238210). OSHA activity number 341206100.
Where did this inspection happen?
- Establishment
- DEES ELECTRICAL, INC.
- Site address
- 978 WHITE CIR
- City
- HINESVILLE
- State
- GA
- ZIP
- 31313
- Mailing
- P.O. BOX 101, HINESVILLE, GA 31310
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 25
- Ownership type
- A
Citations
2 citations on file for this inspection.
1926.403 B02
- Issued
- Penalty
- Initial $1700.00 · Current $1020.00 Reduced
General-duty citation text
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification: a) Temporary Power at Jobsite- on or about January 26, 2016, Dees Electrical, Inc. installed an 4-inch X 4-inch electrical handy box that was designed to be secured and mounted. The electrical handy box was lying on the ground and hard wired to the temporary power pole. The electrical handy box was used by the siding sub-contractor employees to support electric power to hand tools, thereby exposing sub-contractor employees to shock and electrical hazards.
Recent events (2)
- — I (S) $1020
- — Z (S) $1700
1926.404 B01 II
- Issued
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1926.404(b)(1)(ii): On a construction site, where an assured equipment grounding program was not utilized, all 120-volt, single-phase, 15 and 20 ampere receptacle outlets which were not a part of the permanent wiring of the building or structure and which are in use by employees did not have approved ground fault circuit interrupters for personal protection. a) Temporary Power Panel - On or about January 26, 2016, employees were allowed to use 4-inch X 4-inch electrical handy box that was designed to be secured and mounted without the use of a Ground Fault Circuit Interrupters (GFCI), exposing employees to shock and electrocution hazards.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections in this industry (NAICS 238210)
PARKVILLE, MD—2026-07-15
THE POWER SOURCE, INC.
SOUTH BARRINGTON, IL—2026-07-15
EDGE ELECTRICAL SYSTEMS, LLC
LAYTON, UT—2026-07-14
LYNN WOODWARD ELECTRIC LLC
BRIDGEPORT, WV—2026-07-14
INFINITY ELECTRIC & SERVICE COMPANY, LLC
ANNAPOLIS, MD—2026-07-14
J.M. MULLEN ELECTRICAL SERVICES, INC.
More inspections in GA
GREENSBORO, GA—2026-07-16
PURE BEAUTY FARMS, INC.
FOREST PARK, GA—2026-07-16
POLYNT COMPOSITES USA INC.
AUGUSTA, GA—2026-07-16
GF CASTING SOLUTIONS AUGUSTA, LLC
CHAMBLEE, GA—2026-07-16
U.S. DEPARTMENT OF TREASURY
DECATUR, GA—2026-07-15
PALLETS ACQUISITION LLC
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341206100.