WHEAT RIDGE, CO ·
OSHA Inspection: VINCENZA'S RESTAURANT & BAKERY
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of VINCENZA'S RESTAURANT & BAKERY in 8000 W. 44TH AVE, WHEAT RIDGE, CO 80033 (NAICS 722511). OSHA activity number 341207231.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- VINCENZA'S RESTAURANT & BAKERY
- Site address
- 8000 W. 44TH AVE
- City
- WHEAT RIDGE
- State
- CO
- ZIP
- 80033
- Mailing
- 8000 W. 44TH AVE, WHEAT RIDGE, CO 80033
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 722511
- Employees
- 15
- Ownership type
- Private (A)
Citations
5 citations on file for this inspection.
1910.305 B02 I
- Issued
- Mar 1, 2016
- Abate by
- Mar 11, 2016
- Penalty
- Initial $1,200 · Current $1,200
General-duty citation text
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose: a) On or about January 27, 2016, and at times prior, the employees were exposed to electrical shock while employees worked around electrical fixtures and junction boxes that did not have covers. 1) Employees were not protected from electrical shock in that an electrical fixture inside the walk-in freezer door was missing a cover. 2) Employees were not protected from electrical shock in that a junction box underneath the dishwasher station table was missing a cover.
Recent events (1)
- · Z (S) $1200
1910.303 B06
- Issued
- Mar 1, 2016
- Abate by
- Mar 11, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(6): Conductors or equipment were located in damp or wet locations; were exposed to gases, fumes, vapors, liquids, or other agents that have a deteriorating effect on the conductors or equipment; or were exposed to excessive temperatures: a) On or about January 27, 2016, and times prior, employees were exposed to electrical hazards, where the conductors in the bottom of the cooling unit in the freezer were enclosed in ice and therefore subjected to deterioration and corrosion. b) On or about January 27, 2016, and times prior, the junction box underneath the dishwasher table was exposed to corrosion from moisture.
Recent events (1)
- · Z (S) $0
1910.305 G01 IV C
- Issued
- Mar 1, 2016
- Abate by
- Mar 11, 2016
- Penalty
- Initial $1,200 · Current $1,200
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(C): Flexible cords, were run through doorways, windows, or similar openings: a) On or about January 27, 2016 and at times prior, the employer exposed employees to fire hazards due to utilizing extension cords that were run through the doorway of the walk-in freezer to power portable fans located against the back wall in the walk-in freezer.
Recent events (1)
- · Z (S) $1200
1910.305 G01 IV D
- Issued
- Mar 1, 2016
- Abate by
- Mar 11, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords were attached to building surfaces: a) On or about January 27, 2016 and at times prior, the employer exposed employees to fire hazards due to utilizing extension cords that were attached to the wall in the dough preparation work area.
Recent events (1)
- · Z (S) $0
1910.303 B02
- Issued
- Mar 1, 2016
- Abate by
- Mar 11, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling. a) On or about January 27, 2016, and times prior, employees were exposed to fire hazards, where the portable fans were not used appropriately according to instructions included in the listing or labeling. These fans were used as a substitute for permanent fans on the condenser unit which had been removed.