GRAND JUNCTION, CO —
OSHA Inspection: ORICA GROUND SUPPORT
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of ORICA GROUND SUPPORT in 2306 HWY 6 & 50, GRAND JUNCTION, CO 81505 (NAICS 325998). OSHA activity number 341207587.
Where did this inspection happen?
- Establishment
- ORICA GROUND SUPPORT
- Site address
- 2306 HWY 6 & 50
- City
- GRAND JUNCTION
- State
- CO
- ZIP
- 81505
- Mailing
- 150 SUMMER COURT, GEORGETOWN, KY 40324
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 325998
- Employees
- 16
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.303 G01 I
- Issued
- Abate by
- Penalty
- Initial $3825.00 · Current $3825.00
General-duty citation text
29 CFR 1910.303(g)(1)(i): The dimension of the working space in the direction of access to live parts operating 600 volts or less, and likely to require examination, adjustment, servicing, or maintenance while alive, was less than indicated in Table S1: a) Orica Ground Support, 2306 Hwy 6 & 50, Grand Junction, CO 81505: On or before January 14, 2016 the employer did not ensure that the disconnect for the tensile testing area were not obstructed. Employees needed access to the disconnect to disengage the electrical circuits. The employer did not ensure that the dimension of the working space in front of this electrical equipment was at least 3 feet, in accordance with Table S1. This condition exposed employees to electrical hazards.
Recent events (2)
- — I (O) $3825
- — Z (S) $3825
1910.303 E01
- Issued
- Abate by
- Penalty
- Initial $0.00 · Current $0.00
General-duty citation text
29 CFR 1910.303(e)(1): Identification of manufacturer and ratings: Electric equipment was used but the following markings were not in place on the equipment: (i) The manufacturers name, trademark, or other descriptive marking by which the organization responsible for the product may be identified. (ii) Other markings giving voltage, current, wattage, or other ratings as necessary. a) Orica Ground Support, 2306 Hwy 6 & 50, Grand Junction, CO 81505: On or before January 14, 2016, the employer did not ensure that the electrical panels next to the electric Threader were labeled with the manufacturer's name, trademark, or other markings giving voltage, current, wattage, or other ratings as necessary. This condition exposed employees to electrical hazards.
Recent events (2)
- — I (O) $0
- — Z (S) $0
More inspections in this industry (NAICS 325998)
CHARLOTTE, TX—2026-07-07
CLEMENTS FLUIDS
KINDRED, ND—2026-06-29
ICE CRYSTAL ENGINEERING
WAYNESVILLE, NC—2026-06-23
161409 - PREMIER MAGNESIA, LLC
SOUTH PLAINFIELD, NJ—2026-06-17
AVINTHIA INC
WARMINSTER, PA—2026-06-12
CRC INDUSTRIES, INCORPORATED
More inspections in CO
CASTLE ROCK, CO—2026-07-10
MASTER MAGNETICS, INC.
STRASBURG, CO—2026-07-08
JUNIOR ROOFING LLC
FORT COLLINS, CO—2026-07-08
EDWARDS SEMICONDUCTOR SOLUTIONS LLC
CENTENNIAL, CO—2026-07-08
JORDY CONSTRUCTION
HIGHLANDS RANCH, CO—2026-07-08
HOWELL CONSTRUCTION
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341207587.