NEW YORK, NY —
OSHA Inspection: ADVANCED ELECTRIC, INC.
Unprogrammed Other inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Other safety inspection of ADVANCED ELECTRIC, INC. in 190 BOWERY ST, NEW YORK, NY 10029 (NAICS 238210). OSHA activity number 341223113.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ADVANCED ELECTRIC, INC.
- Site address
- 190 BOWERY ST
- City
- NEW YORK
- State
- NY
- ZIP
- 10029
- Mailing
- 252 W. 38TH ST SUITE 1003, NEW YORK, NY 10018
What kind of inspection was it?
- Inspection type
- Unprogrammed Other (I)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 12
- Ownership type
- A
Citations
3 citations on file for this inspection.
1926.405 A02 II B
- Issued
- Apr 22, 2016
- Abate by
- Apr 28, 2016
- Penalty
- Initial $2,000 · Current $1,000 Reduced
General-duty citation text
29 CFR 1926.405(a)(2)(ii)(B): Each temporary wiring branch circuit run as open conductors supplying receptacles or fixed equipment did not contain a separate equipment grounding conductor. a)190 Bowery St, Manhattan, NY, Cabinet Box 6th floor, On or about 1/27/16: A temporary wiring circuit used to power hand tools and receptacles did not have its grounding wire attached to the grounding circuit.
Recent events (2)
- — I (S) $1000
- — Z (S) $2000
1926.405 D
- Issued
- Apr 22, 2016
- Abate by
- Apr 28, 2016
- Penalty
- Initial $2,800 · Current $1,400 Reduced
General-duty citation text
29 CFR 1926.405(d): Panelboards mounted in cabinets, cutout boxes or enclosures designed for the purpose were not dead front: a) 190 Bowery St, Manhattan, NY, 6th, 5th and second floor Power Panel boxes. On or about 1/27/16: Panel boxes used for temporary wiring circuits were not fully enclosed to prevent personnel from coming into contact with energized parts located with in the panel box.
Recent events (2)
- — I (S) $1400
- — Z (S) $2800
1926.405 G02 IV
- Issued
- Apr 22, 2016
- Abate by
- May 4, 2016
- Penalty
- Initial $1,600 · Current $800 Reduced
General-duty citation text
29 CFR 1926.405(g)(2)(iv): Flexible cords were not connected to devices and fittings so that strain relief is provided to prevent pull from being directly transmitted to joints or terminal screws. a) 190 Bowery St, Manhattan, NY, On or about 1/27/16: Temporary flexible power cords were not connected to strain relief devices as they entered/exited the panel boxes.
Recent events (2)
- — I (S) $800
- — Z (S) $1600
More inspections at Advanced Electric, INC.
View Advanced Electric, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 238210)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341223113.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.