Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ADVANCED ELECTRIC, INC.

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of ADVANCED ELECTRIC, INC. in 190 BOWERY ST, NEW YORK, NY 10029 (NAICS 238210). OSHA activity number 341223113.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Advanced Electric, INC. — free Get an email when a new federal OSHA severe-injury report for Advanced Electric, INC. is published. One employer, no account, unsubscribe in one click.
Site address
190 BOWERY ST
City
NEW YORK
State
NY
ZIP
10029
Mailing
252 W. 38TH ST SUITE 1003, NEW YORK, NY 10018
Inspection type
Unprogrammed Other (I)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
12
Ownership type
A

3 citations on file for this inspection.

1926.405 A02 II B

Serious Gravity 5 1 instance 1 exposed
Issued
Apr 22, 2016
Abate by
Apr 28, 2016
Penalty
Initial $2,000 · Current $1,000 Reduced
29 CFR 1926.405(a)(2)(ii)(B): Each temporary wiring branch circuit run as open conductors supplying receptacles or fixed equipment did not contain a separate equipment grounding conductor.    a)190 Bowery St, Manhattan, NY, Cabinet Box 6th floor, On or about 1/27/16: A temporary wiring circuit used to power hand tools and receptacles did not have its grounding wire attached to the grounding circuit.
Recent events (2)
  • — I (S) $1000
  • — Z (S) $2000

1926.405 D

Serious Gravity 10 3 instances 3 exposed
Issued
Apr 22, 2016
Abate by
Apr 28, 2016
Penalty
Initial $2,800 · Current $1,400 Reduced
29 CFR 1926.405(d): Panelboards mounted in cabinets, cutout boxes or enclosures designed for the purpose were not dead front:    a) 190 Bowery St, Manhattan, NY, 6th, 5th and second floor Power Panel boxes. On or about 1/27/16: Panel boxes used for temporary wiring circuits were not fully enclosed to prevent personnel from coming into contact with energized parts located with in the panel box.
Recent events (2)
  • — I (S) $1400
  • — Z (S) $2800

1926.405 G02 IV

Serious Gravity 5 3 instances 3 exposed
Issued
Apr 22, 2016
Abate by
May 4, 2016
Penalty
Initial $1,600 · Current $800 Reduced
29 CFR 1926.405(g)(2)(iv): Flexible cords were not connected to devices and fittings so that strain relief is provided to prevent pull from being directly transmitted to joints or terminal screws.    a) 190 Bowery St, Manhattan, NY, On or about 1/27/16:  Temporary flexible power cords were not connected to strain relief devices as they entered/exited the panel boxes.
Recent events (2)
  • — I (S) $800
  • — Z (S) $1600

View Advanced Electric, INC.'s full OSHA safety record →