Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,196,991Inspections Most recent open 2026-08-24 Last loaded 2026-08-27

OSHA Inspection: PORTSMOUTH MARINE TERMINAL

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of PORTSMOUTH MARINE TERMINAL in 2000 SEABOARD AVENUE, PORTSMOUTH, VA 23707 (NAICS 488320). OSHA activity number 341225696.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Portsmouth Marine Terminal for free Get an email when a new federal OSHA severe-injury report for Portsmouth Marine Terminal is published. One employer, no account, unsubscribe in one click.
Site address
2000 SEABOARD AVENUE
City
PORTSMOUTH
State
VA
ZIP
23707
Mailing
1000 VIRGINIA INTERNATIONAL GATEWAY BLVD, PORTSMOUTH, VA 23703
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
488320
Employees
150
Ownership type
Private (A)

3 citations on file for this inspection.

1910.334 B02

Serious Gravity 5 1 instance 4 exposed
Issued
Mar 30, 2016
Abate by
Apr 25, 2016
Penalty
Initial $5,100 · Current $5,100
29 CFR 1910.334(b)(2): After a circuit was de-energized by a circuit protective device, the circuit was manually reenergized without determining that the equipment and circuit can be safely energized.  a)    Portsmouth Marine Terminal: On or about 01/28/2016, the circuit breaker in pit #8 tripped resulting from a fault in the shore power cable. The circuit breaker was reclosed without determining the circuit was safe, an arc flash occurred resulting in facial burns to an employee.  Abatement certification required within 10 days after abatement date.  The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (2)
  • · I (S) $5100
  • · Z (S) $5100

1910.335 A01 I

Serious Gravity 10 1 instance 4 exposed
Issued
Mar 30, 2016
Abate by
Apr 25, 2016
Penalty
Initial $7,000 · Current $3,500 Reduced
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed:  a)      Portsmouth Marine Terminal, Pit #8: On or about 01/28/2016, an employee was not provided protection from possible electric shock in that rubber insulated gloves were not used in testing exposed 480 volts conductors.     Abatement certification and documentation required within 10 days after abatement date. The certification shall include a statement that abatement is complete, the date and method of abatement, and state that employees and their representatives were informed of this abatement. Abatement documentation shall include documents demonstrating that abatement is complete, such as evidence of the purchase or repair of equipment, photographic or video evidence of abatement or other written records.
Recent events (2)
  • · I (S) $3500
  • · Z (S) $7000

1910.335 A01 V

Other-than-serious 1 instance 4 exposed
Issued
Mar 30, 2016
Abate by
Apr 25, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.335(a)(1)(v): Employees exposed to the danger of injury to the eyes or face from electric arcs or flashes or from flying objects resulting from electrical explosion did not wear protective equipment for the eyes or face:    a)      Portsmouth Marine Terminal, Pit #8: On or about 01/28/2016, employees working with 480 volts were not required to wear a face shield while troubleshooting shore power as a result a 480 volts plug arc flashed causing facial burns to an employee.     Abatement certification required within 10 days after abatement date.  The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.
Recent events (2)
  • · I (O) $0
  • · Z (S) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 341225696.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.