MCCHORD AFB, WA —
OSHA Inspection: DEFENSE COMMISSARY AGENCY; MCCHORD COMMISSARY
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of DEFENSE COMMISSARY AGENCY; MCCHORD COMMISSARY in 577 LINCOLN BLVD., MCCHORD AFB, WA 98438 (NAICS 445110). OSHA activity number 341226850.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- DEFENSE COMMISSARY AGENCY; MCCHORD COMMISSARY
- Site address
- 577 LINCOLN BLVD.
- City
- MCCHORD AFB
- State
- WA
- ZIP
- 98438
- Mailing
- 577 LINCOLN BLVD., JOINT BASE LEWIS MCCHORD, WA 98438
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 445110
- Employees
- 115
- Ownership type
- D
Citations
4 citations on file for this inspection.
1910.303 B02
- Issued
- Mar 11, 2016
- Abate by
- Apr 27, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled equipment was not installed and used in accordance with any instructions included in the listing or labeling: a) CAO/QAE Office, where a relocatable power tap was used to supply power to appliances including, the Magic Chef microwave oven and the Hamilton Beach toaster. The Defense Commissary Agency was previously cited for a violation of this standard which was contained in OSHA inspection no. 314898974, citation no. 1, item no. 1, issued on April 21, 2011 with respect to a workplace at Marysville, WA.
Recent events (1)
- — Z (R) $0
1910.303 G01 II
- Issued
- Mar 11, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(ii): Working space for equipment likely to require examination, adjustment, servicing, or maintenance while energized was used for storage: a) Cashier Cage, where items including a trash can, a bucket, a fan, and walking canes were stored in front of circuit panel CS.
Recent events (1)
- — Z (O) $0
1910.305 B02 I
- Issued
- Mar 11, 2016
- Abate by
- Apr 27, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: a) CAO/QAE Office, where the outlet located adjacent to the air conditioner was equipped with a damaged face plate.
Recent events (1)
- — Z (O) $0
1910.305 J01 IV
- Issued
- Mar 11, 2016
- Abate by
- Apr 27, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(j)(1)(iv): Fixtures installed in wet or damp locations were not approved for the purpose and were not so constructed or installed that water could not enter or accumulate in wireways, lamp holders or other electrical parts: a) Main Receiving Dock, where a receptacle located outdoors was not equipped with a cover.
Recent events (1)
- — Z (O) $0
More inspections at Defense Commissary Agency; Mcchord Commissary
View Defense Commissary Agency; Mcchord Commissary's full OSHA safety record →