Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: SPECTRUM ELECTRIC, LLC.

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of SPECTRUM ELECTRIC, LLC. in 185 ATLANTIC AVE., BROOKLYN, NY 11223 (NAICS 238210). OSHA activity number 341240349.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Spectrum Electric, LLC. — free Get an email when a new federal OSHA severe-injury report for Spectrum Electric, LLC. is published. One employer, no account, unsubscribe in one click.
Site address
185 ATLANTIC AVE.
City
BROOKLYN
State
NY
ZIP
11223
Mailing
195 BAY 19TH STREET, BROOKLYN, NY 11223
Inspection type
Unprogrammed Other (I)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
2
Ownership type
A

3 citations on file for this inspection.

1926.404 B01 II

Serious Gravity 10 3 instances 1 exposed
Issued
Apr 4, 2016
Abate by
Apr 14, 2016
Penalty
Initial $2,800 · Current $1,520 Reduced
29 CFR 1926.404(b)(1)(ii): Ground-fault circuit interrupters. All 120-volt, single-phase 15- and 20-ampere receptacle outlets on construction sites, which are not a part of the permanent wiring of the building or structure and which are in use by employees, shall have approved ground-fault circuit interrupters for personnel protection. Receptacles on a two-wire, single-phase portable or vehicle-mounted generator rated not more than 5kW, where the circuit conductors of the generator are insulated from the generator frame and all other grounded surfaces, need not be protected with ground-fault circuit interrupters.    a.) 185 Atlantic Ave Brooklyn, NY 11223      Employees throughout the jobsite were observed engaged in construction activities in areas where approved ground-fault circuit interrupters for personnel protection was not available there-by exposing employee(s) to electrical hazards.        Violation was observed on or about 01/29/16
Recent events (2)
  • — I (S) $1520
  • — Z (S) $2800

1926.404 F06

Serious Gravity 5 2 instances 1 exposed
Issued
Apr 4, 2016
Penalty
Initial $2,400 · Current $1,520 Reduced
29 CFR 1926.404(f)(6): The path to ground from circuits, equipment, or enclosures was not permanent and continuous:      a) Jobsite at 185 Atlantic Ave. Brooklyn, NY: The flexible extension cord connected to the electric drill was not grounded, exposing employees to electrocution hazards, on or about 01/29/16.
Recent events (2)
  • — I (S) $1520
  • — Z (S) $2400

1926.405 J02

Serious Gravity 5 1 instance 1 exposed
Issued
Apr 4, 2016
Penalty
Initial $2,400 · Current $1,520 Reduced
29 CFR 1926.405(j)(2): Receptacles, cord connectors, and attachment plugs (caps) -    a) Jobsite at 185 Atlantic Ave. Brooklyn, NY: A wall mounted 110 volt electrical outlet used to power electrical equipment was not secured to the box, thus exposing employees to electrocution hazards, on or about 01/29/16.
Recent events (2)
  • — I (S) $1520
  • — Z (S) $2400

View Spectrum Electric, LLC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341240349.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.