Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,196,991Inspections Most recent open 2026-08-24 Last loaded 2026-08-27

OSHA Inspection: PACIFIC HIDE AND FUR DEPOT

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of PACIFIC HIDE AND FUR DEPOT in 777 4TH AVE NORTH, BILLINGS, MT 59101 (NAICS 423930). OSHA activity number 341255594.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Pacific Hide and FUR Depot for free Get an email when a new federal OSHA severe-injury report for Pacific Hide and FUR Depot is published. One employer, no account, unsubscribe in one click.
Site address
777 4TH AVE NORTH
City
BILLINGS
State
MT
ZIP
59101
Mailing
777 4TH AVE NORTH, BILLINGS, MT 59101
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
423930
Employees
4
Ownership type
Private (A)

5 citations on file for this inspection.

1910.178 F02

Other-than-serious 1 instance 4 exposed
Issued
Jun 3, 2016
Abate by
Jun 29, 2016
Penalty
Initial $2,550 · Current $1,275 Reduced
29 CFR 1910.178(f)(2): The storage and handling of liquefied petroleum gas fuel was not in accordance with NFPA Storage and Handling of Liquefied Petroleum Gases (NFPA No. 58-1969), which is incorporated by reference as specified in Sec. 1910.6:    a) East wall of facility: On or about February 17, 2016 and at times prior, employees exposed to the hazards associated with permanent storage of liquefied petroleum gas fuel near the employee office entrance door. This door is used for entry and exit through-out the work day.
Recent events (2)
  • · I (O) $1275
  • · Z (S) $2550

1910.303 B07 IV

Other-than-serious 1 instance 4 exposed
Issued
Jun 3, 2016
Abate by
Jun 29, 2016
Penalty
Initial $3,400 · Current $1,700 Reduced
29 CFR 1910.303(b)(7)(iv): Electrical equipment had damaged parts that may adversely affect safe operation or mechanical strength of the equipment, such as parts that are broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating:    a) Outlet south end of facility (entry) overhead door area: On or about February 17, 2016 and at times prior, employees exposed to shock and burn hazards while using the defective outlet.
Recent events (2)
  • · I (O) $1700
  • · Z (S) $3400

1910.305 B01 II

Serious Gravity 5 2 instances 4 exposed
Issued
Jun 3, 2016
Abate by
Jun 29, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:  a) Outlet south end of facility (entry) overhead door area: On or about February 17, 2016 and at times prior, employees exposed to shock and burn hazards while using outlet fixture with openings (knock-outs) not closed.  b) Outlet south end of facility (entry) overhead door area: On or about February 17, 2016 and at times prior, employees exposed to shock and burn hazards while using outlet fixture with center opening to outlet fixture not closed.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.305 B02 I

Serious Gravity 5 1 instance 4 exposed
Issued
Jun 3, 2016
Abate by
Jun 29, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy:  a) Outlet near office in front entry: On or about February 17, 2016 and at times prior, employees exposed to shock and burn hazards while using the defective outlet.
Recent events (2)
  • · I (S) $0
  • · Z (S) $0

1910.37 B06

Deleted Other-than-serious 1 instance 4 exposed
Issued
Jun 3, 2016
Abate by
Jun 29, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(6): Each exit sign must be illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color:   a) EXIT sign located above walk through exit door on the north east corner of the building: On or about February 17, 2016 and at times prior, employees exposed entrapment hazards when the designated emergency exit did not illuminate to be clearly visible in the event of an emergency.
Recent events (2)
  • · I (O) $0
  • · Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 341255594.