Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ABCO FIRE PROTECTION

Referral inspection · Health discipline

On , OSHA opened a referral health inspection of ABCO FIRE PROTECTION in 3319 ST. LAWRENCE DR., TOLEDO, OH 43604 (NAICS 238990). OSHA activity number 341257731.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Abco Fire Protection — free Get an email when a new federal OSHA severe-injury report for Abco Fire Protection is published. One employer, no account, unsubscribe in one click.
Site address
3319 ST. LAWRENCE DR.
City
TOLEDO
State
OH
ZIP
43604
Mailing
115 S. ERIE ST., TOLEDO, OH 43604
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238990
Employees
17
Ownership type
A

2 citations on file for this inspection.

1915.506 B01

Serious Gravity 5 1 instance 3 exposed
Issued
May 6, 2016
Abate by
Jun 1, 2016
Penalty
Initial $3,600 · Current $2,160 Reduced
29 CFR 1915.506(b)(1): The employer did not physically isolate the fixed extinguishing systems or utilize other positive means to prevent the systems discharge before work was done in that space which system was located.     A. On or about February 9, 2016, the employer did not ensure that the fixed fire extinguishing system was properly isolated to prevent discharge during a required system check.  Employees performing the fire system check did not ensure that all the Halon bottles were disconnected before performing their routine test.  Halon was discharged into several areas of the ship requiring evacuation.
Recent events (2)
  • — I (S) $2160
  • — Z (S) $3600

1915.506 E02

Serious Gravity 5 1 instance 2 exposed
Issued
May 6, 2016
Abate by
Jun 1, 2016
Penalty
Initial $3,600 · Current $2,160 Reduced
29 CFR 1915.506(e)(2): When testing a fixed extinguisher system did not involve a total discharge, the employer did not make sure that the system's extinguishing agent medium was physically isolated and that employees not directly involved in the testing were evacuated from the protected space.     A. On or about February 9, 2016, the employer did not ensure that system's extinguishing agent was physically isolated and employees not directly involved with the testing were evacuated from the protected space.  Employees performing the fire system check did not ensure that all the Halon bottles were disconnected before performing their routine test. Contractors that were working in the engine area and not involved with the testing were not evacuated from the area where Halon could potentially be discharged.
Recent events (2)
  • — I (S) $2160
  • — Z (S) $3600

View Abco Fire Protection's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341257731.