OSHA Inspection: STEINER ELECTRIC INC.

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of STEINER ELECTRIC INC. in 8825 N. 60TH ST., BROWN DEER, WI 53223 (NAICS 238210). OSHA activity number 341262418.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Steiner Electric INC. — free Get an email when a new federal OSHA severe-injury report for Steiner Electric INC. is published. One employer, no account, unsubscribe in one click.
Site address
8825 N. 60TH ST.
City
BROWN DEER
State
WI
ZIP
53223
Mailing
2323 SYLVAN WAY, WEST BEND, WI 53095
Inspection type
Unprogrammed Other (I)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
27
Ownership type
A

4 citations on file for this inspection.

1926.403 B01 I

Other-than-serious 1 instance 4 exposed
Issued
Jun 23, 2016
Abate by
Jun 29, 2016
Penalty
Initial $1,607 · Current $1,000 Reduced
29 CFR 1926.403(b)(1)(i): Safety of equipment was not determined on the basis of suitability of the equipment for an identified purpose as evidenced by listing, labeling, or certification for that identified purpose.    (a) Basement Boiler Room: On or about February 18, 2016 romex electrical cable was not used for its identified purpose.  An electrical plug was attached to the end of the romex cable and plugged into an energized wall outlet.      (b)  Basement Boiler Room:  On or about February 18, 2016 romex electrical cable was used as an electrical extension cord to energize an electrical junction box mounted on the ceiling. A temporary light fixture was wired into the junction box providing the electrical power for the temporary lighting in the boiler room.
Recent events (2)
  • — I (O) $1000
  • — Z (S) $1607

1926.405 G01 III A

Deleted Serious Gravity 1 1 instance 3 exposed
Issued
Jun 23, 2016
Abate by
Jun 29, 2016
Penalty
Initial $0 · Current $0
29 CFR 1926.405(g)(1)(iii)(A): Flexible cord(s) were being used as a substitute for fixed wiring of a structure.  (a) Basement Boiler Room: On or about February 18, 2016 romex electrical cable was not used for its identified purpose.  An electrical plug was attached to the end of the romex cable and plugged into an energized wall outlet.    (b) Basement Boiler Room:  On or about February 18, 2016 romex electrical cable was used as an electrical extension cord to energize an electrical junction box mounted on the ceiling.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.405 A02 II E

Deleted Serious Gravity 1 1 instance 3 exposed
Issued
Jun 23, 2016
Abate by
Jun 29, 2016
Penalty
Initial $1,607 · Current $0 Reduced
29 CFR 1926.405(a)(2)(ii)(E): Lamps used in temporary wiring for general illumination were not protected from accidental contact or breakage:  (a) Basement Boiler Room: On or about February 18, 2016 temporary lighting bulbs did not have protective guards installed exposing the light bulbs to inadvertent contact and breakage.
Recent events (2)
  • — I (S) $0
  • — Z (S) $1607

1926.405 A02 II F

Other-than-serious 1 instance 3 exposed
Issued
Jun 23, 2016
Abate by
Jun 29, 2016
Penalty
Initial $0 · Current $0
29 CFR 1926.405(a)(2)(ii)(F): Temporary lights were suspended by their electric cords when such lights and cords were not designed for suspension:    (a) Basement Boiler Room: On or about February 18, 2016 a temporary romex electrical lighting cord was suspended over a three (3) inch schedule 40 pipe.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

View Steiner Electric INC.'s full OSHA safety record →