SAINT AUGUSTINE, FL —
OSHA Inspection: CA-PAR ELECTRIC, INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of CA-PAR ELECTRIC, INC. in 9600 CR 13 N, SAINT AUGUSTINE, FL 32092 (NAICS 238210). OSHA activity number 341265874.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CA-PAR ELECTRIC, INC.
- Site address
- 9600 CR 13 N
- City
- SAINT AUGUSTINE
- State
- FL
- ZIP
- 32092
- Mailing
- 63396 OLD MILITARY RD., PEARL RIVER, LA 70452
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 1
- Ownership type
- A
Citations
5 citations on file for this inspection.
1926.960 C02 II B
- Issued
- Apr 1, 2016
- Abate by
- Apr 13, 2016
- Penalty
- Initial $2,975 · Current $0 Reduced
General-duty citation text
29 CFR 1926.960(c)(2)(ii)(B): Removed the rubber insulating gloves and sleeves until he or she is in a position where he or she cannot reach into the minimum approach distance, established by the employer under paragraph (c)(1) of this section: a. On February 8, 2016, employees occasionally remove their rubber gloves while elevated in the bucket near energized overhead power lines rated at 23,000 volts, exposing themselves to an electrical hazard.
Recent events (2)
- — I (S) $0
- — Z (S) $2975
1926.960 G02
- Issued
- Apr 1, 2016
- Abate by
- Jul 22, 2016
- Penalty
- Initial $2,975 · Current $3,000
General-duty citation text
29 CFR 1926.960(g)(2): Estimate of available heat energy. For each employee exposed to hazards from electric arcs, the employer did not make a reasonable estimate of the incident heat energy to which the employee would be exposed: a. On February 8, 2016, for overhead power line work near energized lines, the employer did not estimate the incident heat energy in order to determine the proper personal protective equipment.
Recent events (2)
- — I (S) $3000
- — Z (S) $2975
1926.960 G05 IV
- Issued
- Apr 1, 2016
- Abate by
- Apr 13, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.960(g)(5)(iv): The protection for the employee's head did not consist of head protection meeting � 1926.100(b)(2) and a faceshield with a minimum arc rating of 8 cal/cm2 if the estimated incident energy exposure is less than 13 cal/cm2 for exposures involving single-phase arcs in open air or 9 cal/cm2 for other exposures: a. On February 8, 2016, employees working near energized overhead power lines are not wearing face shields, exposing themselves to an electric arc blast.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1904.7 A
- Issued
- Apr 1, 2016
- Abate by
- Apr 11, 2016
- Penalty
- Initial $595 · Current $0 Reduced
General-duty citation text
29 CFR 1904.7(a): The employer did not record workplace injuries and illnesses that would be considered to meet the general recording criteria, and therefore to be recordable: a. On or about February 18, 2016, the employer did record the injury of an employee that was hospitalized on February 8, 2016.
Recent events (2)
- — I (O) $0
- — Z (O) $595
1904.39 A02
- Issued
- Apr 1, 2016
- Abate by
- Apr 13, 2016
- Penalty
- Initial $2,975 · Current $0 Reduced
General-duty citation text
29 CFR 1904.39(a)(2): The employer did not report an in-patient hospitalization, amputation, or loss of an eye as a result of a work-related incident to OSHA within twenty-four (24) hours: a. On February 18, 2016, the employer did not report that an employee that was involved in a work place incident that resulted in a hospitalization on February 8, 2016.
Recent events (2)
- — I (O) $0
- — Z (O) $2975
More inspections at Ca-Par Electric, INC.
View Ca-Par Electric, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 238210)
More inspections in FL