DAYTON, OH —
OSHA Inspection: MAHLE BEHR DAYTON L.L.C.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of MAHLE BEHR DAYTON L.L.C. in 1600 WEBSTER ST., DAYTON, OH 45404 (NAICS 336391). OSHA activity number 341266484.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- MAHLE BEHR DAYTON L.L.C.
- Site address
- 1600 WEBSTER ST.
- City
- DAYTON
- State
- OH
- ZIP
- 45404
- Mailing
- 1600 WEBSTER ST., DAYTON, OH 45404
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 336391
- Employees
- 1100
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.147 C04 II B
- Issued
- Mar 16, 2016
- Abate by
- Apr 11, 2016
- Penalty
- Initial $5,000 · Current $5,000
General-duty citation text
29 CFR 1910.147(c)(4)(ii)(B): Specific procedural steps for shutting down, isolating, blocking and securing machines or equipment to control hazardous energy; The specific energy control procedure for the Radiator Furnace Conveyor Line involving electrical, 480 Volts AC and pneumatic, 90 psi, energy sources did not include the specific techniques for the control of these hazardous energy sources.
Recent events (3)
- — F (S) $5000
- — C (S) $5000
- — Z (S) $5000
1910.147 C06 I B
- Issued
- Mar 16, 2016
- Abate by
- Apr 18, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(6)(i)(B): The periodic inspection shall be conducted to correct any deviations or inadequacies identified. The Company had not ensured that the review of the energy control procedures corrected the inadequacies in the specific energy control procedure for the Hytrol Furnace Conveyor Lines, Model ABEZ.
Recent events (3)
- — F (S) $0
- — C (S) $0
- — Z (S) $0
1910.147 F01
- Issued
- Mar 16, 2016
- Abate by
- Apr 18, 2016
- Penalty
- Initial $7,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.147(f)(1): Testing or positioning of machines, equipment or components thereof. In situations in which lockout or tagout devices must be temporarily removed from the energy isolating device and the machine or equipment energized to test or position the machine, equipment or component thereof, the following sequence of actions shall be followed: Employee performing testing or positioning of machines, equipment did not perform the following: deenergize all systems and reapply energy control procedures in accordance with paragraph (d) to continue servicing and maintenance. On or about February 14, 2016, in the Production Area, Core Build 2, a general maintenance employee was replacing a sprocket and tightening the tension on the chain on the Hytrol Conveyor, E-44, when the following sequence was not followed prior to completion of the maintenance activity.
Recent events (3)
- — F (S) $0
- — C (S) $7000
- — Z (S) $7000
More inspections in this industry (NAICS 336391)
More inspections in OH
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341266484.