OSHA Inspection: NEW ENGLAND WIRE PRODUCTS, INC

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of NEW ENGLAND WIRE PRODUCTS, INC in 1121 INDUSTRIAL BLVD., GREENSBORO, GA 30642 (NAICS 332618). OSHA activity number 341274256.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch NEW England Wire Products, INC for free Get an email when a new federal OSHA severe-injury report for NEW England Wire Products, INC is published. One employer, no account, unsubscribe in one click.
Site address
1121 INDUSTRIAL BLVD.
City
GREENSBORO
State
GA
ZIP
30642
Mailing
1121 INDUSTRIAL BLVD., GREENSBORO, GA 30642
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332618
Employees
30
Ownership type
Private (A)

5 citations on file for this inspection.

1910.36 D01

Serious Gravity 10 1 instance 6 exposed
Issued
May 9, 2016
Abate by
Jun 3, 2016
Penalty
Initial $4,900 · Current $4,900
29 CFR 1910.36(d)(1): Employee(s) were not able to open an exit route door from the inside at all times without keys, tools, or special knowledge:   On or about 02/23/16, located in the warehouse storage area, right corner the door was locked and required a key to open.
Recent events (3)
  • · C (S) $4900
  • · W (S) $4900
  • · Z (S) $4900

1910.37 A04

Serious Gravity 5 1 instance 6 exposed
Issued
May 9, 2016
Abate by
Jun 3, 2016
Penalty
Initial $2,800 · Current $2,800
29 CFR 1910.37(a)(4): Safeguard(s) designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting), were not in proper working order at all times:  On or about 2/23/16 located in the warehouse, left door press break area door: The exit signs light were out and were very hard to locate if there was a power failure.      B). Located in the warehouse right and left corners entrance door exit sign light out  C). Located in the Machine shop area door exit sign light out
Recent events (3)
  • · C (S) $2800
  • · W (S) $2800
  • · Z (S) $2800

1910.157 E03

Serious Gravity 5 1 instance 6 exposed
Issued
May 9, 2016
Abate by
Jun 3, 2016
Penalty
Initial $2,800 · Current $2,800
29 CFR 1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check:  On or about 2/23/16 located in the warehouse and storage area the fire extinguishers were not inspected annual.
Recent events (3)
  • · C (S) $2800
  • · W (S) $2800
  • · Z (S) $2800

1910.303 G01 IV B

Serious Gravity 5 1 instance 3 exposed
Issued
May 9, 2016
Abate by
Jun 3, 2016
Penalty
Initial $2,800 · Current $2,800
29 CFR 1910.303(g)(1)(iv)(B): Where the working space required by paragraph (g)(1)(i) of this section is doubled, only one entrance to the working space is required; however, the entrance shall be located so that the edge of the entrance nearest the equipment is the minimum clear distance given in Table S-1 away from such equipment.  On or about 2/23/16 located in the warehouse at section A storage area left corner: The electrical panel board was blocked with a large spoils of wire racks with a zero clearance.
Recent events (3)
  • · C (S) $2800
  • · W (S) $2800
  • · Z (S) $2800

1910.305 G01 IV

Serious Gravity 5 1 instance 3 exposed
Issued
May 9, 2016
Abate by
Jun 3, 2016
Penalty
Initial $2,800 · Current $2,800
29 CFR 1910.305(g)(1)(iv): Flexible cords and/ or cables were used for purposes prohibited by paragraphs (A) through (F) of 29 CFR 1910.305(g)(1)(iv):  On or about 2/23/15 located in main office area: The computers, printers and extension cords were plugged in to two temporary wiring Power Strips & Multi-Outlet, a flexible extension cord was used for over three years.
Recent events (3)
  • · C (S) $2800
  • · W (S) $2800
  • · Z (S) $2800

View NEW England Wire Products, INC's full OSHA safety record →