Safety Incidents OSHA Severe Injury Reports · 2015–2025
2,004,209Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: TEXAS METALS & RECYCLING

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of TEXAS METALS & RECYCLING in 2989 PINE ST., ABILENE, TX 79601 (NAICS 423930). OSHA activity number 341275774.

Watch Texas Metals & Recycling — free Get an email when a new federal OSHA severe-injury report for Texas Metals & Recycling is published. One employer, no account, unsubscribe in one click.
Site address
2989 PINE ST.
City
ABILENE
State
TX
ZIP
79601
Mailing
2989 PINE ST., ABILENE, TX 79601
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
423930
Employees
13
Ownership type
A

4 citations on file for this inspection.

1910.303 F02

Serious Gravity 5 2 instances 5 exposed
Issued
Abate by
Penalty
Initial $1600.00 · Current $960.00 Reduced
29 CFR 1910.303(f)(2):  Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:  The employer did not ensure electrical panel boxes were labeled to indicate what equipment each breaker supplied power to and exposed employees to electrical shock hazards.   1)  120 208 volts 3 phase breaker box in shear building; 2)  110 volts breaker box in new/used steel sales shop.
Recent events (2)
  • — I (S) $960
  • — Z (S) $1600

1910.303 G01

Serious Gravity 5 2 instances 5 exposed
Issued
Abate by
Penalty
Initial $1600.00 · Current $960.00 Reduced
29 CFR 1910.303(g)(1):  Employer did not ensure sufficient access and working space was provided and maintained about all electric equipment to permit ready and safe operation and maintenance of such equipment:  Employees were exposed to electrical shock hazards while working around electrical panels that were blocked by chairs, metal pieces, filters, hoses, ladders, cabinets and other debris:  1)  120 208 volts 3 phase breaker box in shear building; 2)  110 volts breaker box in new/used steel sales shop.
Recent events (2)
  • — I (S) $960
  • — Z (S) $1600

1910.305 B03 II

Serious Gravity 5 2 instances 5 exposed
Issued
Abate by
Penalty
Initial $1600.00 · Current $960.00 Reduced
29 CFR 1910.305(b)(3)(ii):   Pull and junction boxes used on systems rated over 600 volts, nominal, were not closed by suitable covers, securely fastened in place:  The employer did not ensure junction boxes located in the new/used steel sales shop were closed with a cover exposing employees to electrical shock/burns/electrocution hazards:  1)  120 208 volts 3 phase breaker box in shear building; 2)  110 volts breaker box in new/used steel sales shop.
Recent events (2)
  • — I (S) $960
  • — Z (S) $1600

1910.178 M06

Serious Gravity 10 1 instance 4 exposed
Issued
Abate by
Penalty
Initial $2800.00 · Current $1680.00 Reduced
29 CFR 1910.178(m)(6):   Operators were not certified in the safe operation of powered industrial trucks:  Employer did not ensure forklift operators were trained and certified in the safe operations of forklifts on site:  1)  Komatsu 30 forklift.
Recent events (2)
  • — I (S) $1680
  • — Z (S) $2800

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341275774.