SAN DIEGO, CA —
OSHA Inspection: U.S. POSTAL SERVICE - SAN DIEGO
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of U.S. POSTAL SERVICE - SAN DIEGO in 11251 RANCHO CARMEL DRIVE, SAN DIEGO, CA 92199 (NAICS 491110). OSHA activity number 341287753.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- U.S. POSTAL SERVICE - SAN DIEGO
- Site address
- 11251 RANCHO CARMEL DRIVE
- City
- SAN DIEGO
- State
- CA
- ZIP
- 92199
- Mailing
- 11251 RANCHO CARMEL DRIVE, SAN DIEGO, CA 92199
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 491110
- Employees
- 700
- Ownership type
- A
Citations
2 citations on file for this inspection.
1910.178 G11
- Issued
- Jun 16, 2016
- Abate by
- Jun 30, 2016
- Penalty
- Initial $70,000 · Current $42,000 Reduced
General-duty citation text
29 CFR 1910.178(g)(11): Precautions were not taken to prevent open flames, sparks, or electric arcs in battery charging area: On or about February 29, 2016, and at times there prior to, in the battery charging area, the employer did not ensure that precautions were taken to prevent open flames, sparks, or electrical arcs, where: a) The insulation covering on a flexible cord attached to an electric water heater, plugged into the electrical outlet next to the sink, was pulled away approximately one quarter inch from the plug, exposing the wires beneath creating an arc or spark hazard; b) The emergency alarm system was cross-wired such that when the fire alarm was activated, the exhaust ventilation system turned off while the battery charging station remained turned on. This condition allowed the accumulation of flammable gas to be produced by the battery charging process during alarm system testing and during actual emergency situations that could cause an explosion hazard. The United States Postal Service was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.178(g)(11), which was contained in OSHA inspection number 957149, citation number 01, item number 001 and was affirmed as a final order on March 31, 2014, with respect to a workplace located at 15421 Gale Ave, City of Industry, CA 91715. The United States Postal Service was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.178(q)(11), which was contained in OSHA inspection number 895755, citation number 01, item number 004 and was affirmed as a final order on May 31, 2013, with respect to a workplace located at 7001 S Central Ave, Los Angeles, CA 90052. The United States Postal Service was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.178(g)(11), which was contained in OSHA inspection number 315436014, citation number 01, item number 002 and was affirmed as a final order on August 24, 2011, with respect to a workplace located at 7001 S Central Ave, Los Angeles, CA 90052.
Recent events (2)
- — I (R) $42000
- — Z (R) $70000
1910.305 G02 III
- Issued
- Jun 16, 2016
- Abate by
- Jun 30, 2016
- Penalty
- Initial $6,722 · Current $4,033 Reduced
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: On or about February 29, 2016, the employer did not ensure that the flexible cable used to energize the hot water heater in the battery charging room, connected to the electrical outlet near the sink, did not have tension transmitted to the joint or terminal screws of the plug. The cable covering was pulled away one quarter inch exposing employees to electrical hazard from accidental contact with the damaged cable.
Recent events (2)
- — I (S) $4033.2
- — Z (S) $6722
More inspections at U.S. Postal Service - SAN Diego
View U.S. Postal Service - SAN Diego's full OSHA safety record →
More inspections in this industry (NAICS 491110)
More inspections in CA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341287753.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.