Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: RABBIT CREEK PRODUCTS INC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of RABBIT CREEK PRODUCTS INC in 903 N BROADWAY, LOUISBURG, KS 66053 (NAICS 311423). OSHA activity number 341297166.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Rabbit Creek Products INC — free Get an email when a new federal OSHA severe-injury report for Rabbit Creek Products INC is published. One employer, no account, unsubscribe in one click.
Site address
903 N BROADWAY
City
LOUISBURG
State
KS
ZIP
66053
Mailing
P O BOX 1059, LOUISBURG, KS 66053
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311423
Employees
11
Ownership type
A

6 citations on file for this inspection.

1910.305 B01 I

Serious Gravity 5 1 instance 4 exposed
Issued
Jun 27, 2016
Abate by
Jul 22, 2016
Penalty
Initial $1,600 · Current $1,120 Reduced
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasion, and openings through which conductors entered were not effectively closed:  (a) In the bulking room there were two instances where electrical cables were entering junction boxes and the cables were not protected from abrasion and the openings were not effectively closed. Employees were exposed to a shock hazard.  (b) In "the hole" near the air conditioner, electrical cables entering the junction box were not protected from abrasion and the openings were not effectively closed. Employees were exposed to a shock hazard.
Recent events (2)
  • — Z (S) $1600
  • — I (S) $1120

1910.305 B02

Serious Gravity 5 1 instance 1 exposed
Issued
Jun 27, 2016
Abate by
Jul 22, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy:  In "the hole" next to the air conditioner, the receptacle box did not have a cover installed.  Employees were exposed to a shock hazard.
Recent events (2)
  • — Z (S) $0
  • — I (S) $0

1910.305 G01 IV A

Serious Gravity 5 1 instance 4 exposed
Issued
Jun 27, 2016
Abate by
Jul 1, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and cables were used as a substitute for fixed wiring of a structure:  Employees were exposed to a shock hazards in that extension cords were used as a substitute for fixed wiring:  a. Under the loft, the lighting was provided power by brown zip type extension cords.   b. In the "barn", a red and black AWG 12/3 extension cord was plugged in next to the roll-up door and providing power to a travel trailer stored in this location.
Recent events (2)
  • — Z (S) $0
  • — I (S) $0

1910.305 B01 II

Serious Gravity 5 1 instance 1 exposed
Issued
Jun 27, 2016
Abate by
Jul 29, 2016
Penalty
Initial $2,000 · Current $1,400 Reduced
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:   In "the barn" within the breaker panel located to the left of the main door (as you enter) breakers and/or spacers were missing. Employees were exposed to a shock hazards.
Recent events (2)
  • — Z (S) $2000
  • — I (S) $1400

1910.305 D02

Serious Gravity 5 1 instance 2 exposed
Issued
Jun 27, 2016
Abate by
Jul 29, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(d)(2): Panelboards were not mounted in cabinets, cutout boxes, or enclosures designed for the purpose and/or were not dead front:  In "the barn" the breaker panel located to the left of the main door (as you enter) had the cover loosely mounted up-side-down and the cover was not dead front. Employees were exposed to a shock hazard.
Recent events (2)
  • — Z (S) $0
  • — I (S) $0

1910.178 L01 I

Other-than-serious 1 instance 2 exposed
Issued
Jun 27, 2016
Abate by
Aug 12, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.178(l)(1)(i): The employer did not ensure that each powered industrial truck operator was competent to operate a powered industrial truck safely, as demonstrated by the successful completion of the training and evaluation specified in this paragraph (l):  The employer allowed powered industrial truck operators to operate a forklift at the site without having received formal instruction, including operator evaluation (and record retention) to determine their operating capabilities.
Recent events (2)
  • — Z (O) $0
  • — I (O) $0

View Rabbit Creek Products INC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 341297166.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.