CLEARWATER BEACH, FL ·
OSHA Inspection: SAND KEY ASSOCIATES LIMITED PARTNERSHIP
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of SAND KEY ASSOCIATES LIMITED PARTNERSHIP in 1160 GULF BLVD, CLEARWATER BEACH, FL 33767 (NAICS 721110). OSHA activity number 341299766.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- SAND KEY ASSOCIATES LIMITED PARTNERSHIP
- Site address
- 1160 GULF BLVD
- City
- CLEARWATER BEACH
- State
- FL
- ZIP
- 33767
- Mailing
- 1160 GULF BLVD, CLEARWATER BEACH, FL 33767
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 721110
- Employees
- 340
- Ownership type
- Private (A)
Citations
4 citations on file for this inspection.
1910.332 B03
- Issued
- Jun 29, 2016
- Abate by
- Jul 12, 2016
- Penalty
- Initial $3,000 · Current $1,800 Reduced
General-duty citation text
29 CFR 1910.332(b)(3): Qualified persons (i.e. those permitted to work on or near exposed energized parts) were not, at a minimum, trained in and familiar with the following: (i) The skills and techniques necessary to distinguish exposed live parts from other parts of electric equipment, (ii) The skills and techniques necessary to determine the nominal voltage of exposed live parts, and (iii) The clearance distances specified in 1910.333(c) and the corresponding voltages to which the qualified person will be exposed. (a) at the workplace - the employer did not provide training to employees who were exposed to electric shock and other electrical hazards when working on energized electrical parts including, but not limited to, electrical panels and outlets; on or about 3/3/16.
Recent events (2)
- · I (S) $1800
- · Z (S) $3000
1910.333 C02
- Issued
- Jun 29, 2016
- Abate by
- Jul 12, 2016
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.333(c)(2): Persons who were not qualified worked on electric circuit parts or equipment that had not been de-energized under the procedures of paragraph (b) of this section. (a) at the workplace - employees who were not qualified with the required training were exposed to electric shock and other electrical hazards when working on energized electrical parts including, but not limited to, electrical panels and outlets; on or about 3/3/16.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.335 A01 I
- Issued
- Jun 29, 2016
- Abate by
- Jul 6, 2016
- Penalty
- Initial $7,000 · Current $4,200 Reduced
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed: (a) at the workplace - employees who were exposed to thermal burns and other injuries caused by electrical arcs or flashes when working on energized electrical equipment up to 480 volts including, but not limited to, electrical panels were not provided with personal protective equipment including, but not limited to, eye and face protection including those that could be worn over prescription glasses, appropriate hand and arm protection that properly fit each exposed employee, hearing protection, and protective clothing; on or about 2/16/16.
Recent events (2)
- · I (S) $4200
- · Z (S) $7000
1904.39 A02
- Issued
- Jun 29, 2016
- Abate by
- Jul 6, 2016
- Penalty
- Initial $1,000 · Current $600 Reduced
General-duty citation text
29 CFR 1904.39(a)(2): The employer did not report an in-patient hospitalization, amputation, or loss of an eye as a result of a work-related incident to OSHA within twenty-four (24) hours: (a) The employer did not report an employee's in-patient hospitalization that occurred on 2/16/16 due to thermal burns caused by an electrical arc flash within 24 hours.
Recent events (2)
- · I (O) $600
- · Z (O) $1000
More inspections in this industry (NAICS 721110)
More inspections in FL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 341299766.