OSHA Inspection: LKK WASH

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of LKK WASH in 18425 DETROIT, LAKEWOOD, OH 44107 (NAICS 811192). OSHA activity number 341312064.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch LKK Wash for free Get an email when a new federal OSHA severe-injury report for LKK Wash is published. One employer, no account, unsubscribe in one click.
Establishment
LKK WASH
Site address
18425 DETROIT
City
LAKEWOOD
State
OH
ZIP
44107
Mailing
18425 DETROIT, LAKEWOOD, OH 44107
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
811192
Employees
5
Ownership type
A

10 citations on file for this inspection.

1910.23 C01

Serious Gravity 10 1 instance 1 exposed
Issued
Apr 18, 2016
Abate by
May 6, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.23(c)(1): Open-sided floors and/or platforms four feet or more above adjacent floor or ground level were not guarded with standard railings (or equivalent) and toeboards:  On or about 3/8/16, the employer failed to ensure that employees required to access the elevated walkway, about 6 feet in height, were provided with standard railings and toeboards.
Recent events (1)
  • · Z (S) $0

1910.132 D02

Serious Gravity 10 1 instance 5 exposed
Issued
Apr 18, 2016
Abate by
May 6, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.132(d)(2): The employer did not verify, through a written certification, that the required workplace hazard assessment had been performed:  On or about 3/8/16, the employer failed to create and certify a workplace hazard assessment.
Recent events (1)
  • · Z (S) $0

1910.303 B02

Serious Gravity 5 1 instance 1 exposed
Issued
Apr 18, 2016
Abate by
May 6, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:   On or about 3/8/16, the employer failed to ensure that the flexible cords, near the control boxes, were not used as permanent wiring, and were not spliced.
Recent events (1)
  • · Z (S) $0

1910.305 G01 IV A

Serious Gravity 1 1 instance 1 exposed
Issued
Apr 18, 2016
Abate by
May 6, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords were being used as a permanent source for wiring:  On or about 3/8/2016, the employer failed to ensure that the service technician did not use flexible cords as permanent wiring. Flexible extension cords were used in the place of permanent wiring in the control panels.
Recent events (1)
  • · Z (S) $0

1910.305 G02 II

Serious Gravity 5 1 instance 1 exposed
Issued
Apr 18, 2016
Abate by
May 6, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(ii): Flexible cords were not used only in continuous lengths without splice or tap:  On or about 3/8/16, the employer failed to ensure that flexible cords were used in continuous lengths without splices. The control panel was wired with flexible cords that were spliced.
Recent events (1)
  • · Z (S) $0

1910.303 B07

Serious Gravity 1 1 instance 2 exposed
Issued
Apr 18, 2016
Abate by
May 6, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(7): Electric equipment was not installed in a neat and workmanlike manner:  On or about 3/8/16, the employer did not ensure that the electrical systems were installed in a workmanlike manner. The wiring and electrical equipment, near the control panels, were not easily identifiable and was installed in an untidy manner.
Recent events (1)
  • · Z (S) $0

1910.303 G02 I

Serious Gravity 10 1 instance 1 exposed
Issued
Apr 18, 2016
Abate by
May 6, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):  On or about 3/8/16, the employer failed to ensure that equipment operating at 50 volts or more, were guarded against accidental contact. The 408V service feeder, near the control panels, had the power cables protruding out of the junction box.
Recent events (1)
  • · Z (S) $0

1910.305 B01 II

Serious Gravity 10 1 instance 1 exposed
Issued
Apr 18, 2016
Abate by
May 6, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:  On or about 3/8/16, the employer failed to ensure that the knockouts of the junction boxes were effectively closed including, but not limited to the 408v service feeder.
Recent events (1)
  • · Z (S) $0

1910.305 B02 I

Serious Gravity 10 1 instance 1 exposed
Issued
Apr 18, 2016
Abate by
May 6, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy:  On or about 3/8/16, the employer failed to ensure that all junction boxes, including but not limited to the 408V service feeder, were provided with faceplates.
Recent events (1)
  • · Z (S) $0

1910.333 A

Serious Gravity 10 1 instance 1 exposed
Issued
Apr 18, 2016
Abate by
May 6, 2016
Penalty
Initial $0 · Current $0
29 CFR 1910.333(a): Safety-related work practices were not employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work was performed near or on equipment or circuits which were or could be energized:  On or about 3/8/16, the employer failed to implement safety-related work practices when employees are expected to work on electrical equipment, including but not limited to the control panels, without de-energizing the system.
Recent events (1)